1. Installation should be made in accordance with the regulations of the Authority Having Jurisdiction, local code authorities, and utility
companies which pertain to this type of water heating equipment.
2. Install the venting system in accordance with these instructions and with the National Fuel Gas Code, ANSI Z223.1/NFPA 54,
CAN/CGA B149, and/or applicable provisions of local building codes.
3. This boiler must be vented with materials, components, and systems listed
and approved for Category IV boilers.
Exhaust vent and intake pipe are to be piped separately. This boiler cannot
share a common exhaust or intake with multiple appliances. Failure to
follow this instruction will result in substantial property damage, severe
personal injury, or death.
NOTE:
To avoid contamination often contained in indoor air, it is best to pipe
all intake combustion air directly to the outdoors.
NOTE:
If exhaust vent pipe system passes through an unheated space, such
as an alcove or attic, the space must be heated or the pipe must be insulated.
The insulation must have an R value sufficient to prevent freezing of the
condensate.
Failure to follow all instructions can result in flue gas spillage and carbon
monoxide emissions, causing severe personal injury or death.
Improper seating of vent pipe gaskets can cause eventual gasket failure and exhaust gas leakage. Ensure the exhaust vent pipe is
properly beveled and seated before insertion into the flue adapter. Failure to do so could result in property damage, severe personal
injury, or death.
Due to the extreme flammability of most glues, cements, solvents, and primers used to join plastic exhaust vent and intake pipes,
explosive solvent vapors must be cleared from all vent piping before start-up. Avoid using excess cement or primer, as this may pool in
the vent pipes. Vent assemblies should be allowed to cure for a period of at least 8 hours before powering a connected appliance.
Failure to fo
llow these instructions will result in substantial property damage, severe personal injury, or death. It is the installers’
responsibility to understand the hazards associated with explosive solvents and take the necessary precautions to avoid these risks.
B. APPROVED MATERIALS FOR EXHAUST VENT AND INTAKE PIPE
APPROVED EXHAUST VENT AND INTAKE PIPE MATERIAL
Item
Material
Standards for Installation in:
United States
Canada
Exhaust vent or Intake pipe
and fittings
PVC schedule 40/80
ANSI/ASTM D1785
PP, CPVC, and PVC venting
must be ULC-S636 Certified.
IPEX is an approved
manufacturer in Canada,
supplying vent material listed to
ULC-S636.
PVC-DWV*
ANSI/ASTM D2665*
CPVC schedule 40/80
ANSI/ASTM F441
Polypropylene
ULCS636
Stainless Steel AL29-4C
Certified for Category IV and
direct vent appliance venting
Certified for Category IV and
direct vent appliance venting
Pipe cement/primer
PVC
ANSI/ASTM D2564
IPEX System 636 Cements &
Primers
CPVC
ANSI/ASTM F493
Table 10
Содержание 500 HL
Страница 12: ...12 LP 446 REV 9 3 14 Figure 2 Dimensions and Specifications ...
Страница 21: ...21 LP 446 REV 9 3 14 H PIPING DIAGRAMS Figure 6 ...
Страница 44: ...44 LP 446 REV 9 3 14 E GAS VALVE Figure 26 Mod Con 500 Gas Valve ...
Страница 52: ...52 LP 446 REV 9 3 14 Figure 33 Mod Con Internal Connection Diagram LP 428 K ...
Страница 71: ...71 LP 446 REV 9 3 14 Figure 36 ...
Страница 72: ...72 LP 446 REV 9 3 14 Figure 37 ...
Страница 73: ...73 LP 446 REV 9 3 14 Figure 38 ...
Страница 74: ...74 LP 446 REV 9 3 14 Figure 39 ...
Страница 77: ...77 LP 446 REV 9 3 14 ...
Страница 78: ...78 LP 446 REV 9 3 14 ...
Страница 79: ...79 LP 446 REV 9 3 14 MAINTENANCE NOTES ...