- 3 -
shock-proof, dust-proof, and moisture-proof structure. It is a commonly used and indispensable
instrument for telecommunications, electric power, meteorology, computer rooms, oil fields,
electronic mechanical installation and maintenance, and industrial enterprises that use
electricity as industrial power or energy. It is suitable for measuring grounding resistance of
various telecommunications, electricity, meteorology, computer rooms, oil fields, power
distribution lines, transmission lines of iron towers, gas stations, factory grounding grids,
lightning rods, etc.
The ground-pile clamp ground resistance tester is controlled by a microprocessor and can
accurately detect ground resistance. It uses fast filtering technology to minimize interference. At
the same time with data storage and data upload functions.
III. Range and accuracy
Measurement
mode
Range
Resolution
Accuracy
Clamp
method
0.02Ω-9.99Ω
0.01Ω
±2%rdg±0.1Ω
10.0Ω-99.9Ω
0.5Ω
±3%rdg±0.5Ω
100Ω-199Ω
1Ω
±5%rdg±1Ω
200Ω-299Ω
5Ω
±10%rdg±5Ω
300-699Ω
10Ω
±15%rdg±10Ω
700Ω-999Ω
20Ω
±20%rdg±20Ω
1.00KΩ-1.19KΩ
30Ω
±25%rdg±30Ω
1.20KΩ-2.00KΩ
50Ω
±35%rdg±50Ω
three or four
wire method
0.01Ω-9.99Ω
0.01Ω
±2%rdg±0.2Ω
10.0Ω-99.9Ω
0.1Ω
±2%rdg±1Ω
100Ω-999Ω
1Ω
±2% rdg±15Ω
1.00KΩ-9.99KΩ
0.01KΩ
±2% rdg±0.1KΩ
10.0KΩ-30.0KΩ
0.1KΩ
±3% rdg±0.5KΩ
AC current
0.100mA -0.999mA
0.001mA
±2.5% rdg±0.1mA
1.00mA -9.99mA
0.01mA
±2.5% rdg±0.5mA
10.0mA -99.9mA
0.1mA
±2.5% rdg±1mA
0.100A-0.999A
0.001A
±2.5% rdg±0.1A
1.00A-9.99A
0.01A
±2.5% rdg±0.5A
10.0A-60.0A
0.1A
±2.5% rdg±1A
Ground
voltage
1.00V-9.99V
0.01V
±2.5% rdg±0.1V
10.0V-99.9V
0.1V
±2.5% rdg±1V
100V-600V
1V
±2.5% rdg±5V
Selection
method
0.30Ω-9.99Ω
0.01Ω
±2% rdg±0.3Ω
10.0Ω-99.9Ω
0.1Ω
±2% rdg±1Ω
100Ω-999Ω
1Ω
±2.5% rdg±15Ω
1.00KΩ-3.00KΩ
0.01KΩ
±3% rdg±0.1KΩ
Soil
resistivity
(
ρ
)
0.00Ωm
~
99.99Ωm
0.01Ωm
ρ=2πaR
(note1)
100.0Ωm
~
999.9Ωm
0.1Ωm
1000Ωm
~
9999Ωm
1Ωm
10.00kΩm
~
99.99kΩm
10Ωm