EASYTEST-COMBI519
EN - 37
6.5.2. AUTO mode
1.
With the arrow keys
(
,
)
select the "AUTO" option in
the "
Mode
" section. The instrument displays a screen like
the one shown to the side. Set the duration of the
measurement in the "
Time
" section and follow the steps
from point 2 to point 5 of §
6.4.
The instrument performs the insulation test between: L-N,
L-PE and N-PE. Since some loads could still be
connected between L-N, the instrument performs a
preliminary test by using 50V as test voltage. If the RL-N
is higher than 50k
, a new insulation test between L-N is
performed by using the Vtest value. Finally, the
instrument performs L-PE and N-PE insulation test.
M
15/10 – 18:04
RL-N
=
- - - M
Vt
=
- - - V
RL-PE = - - - M
Vt = - - - V
RN-PE = - - - M
Vt = - - - V
AUTO 500V 1.00M
MODE
Vtest Lim.
2.
Press the
GO/STOP
key on the instrument or the
START
key on the remote switch probe. The instrument starts the
automatic sequential measurement of the insulation
resistance between L-N, L-PE and N-PE respectively by
showing the "
Measuring…
" message. The instrument
shows the message "
OK
" on the display in case of a
positive result of each test (value higher than the set
minimum limit threshold) or "
NOT OK
" in case of a
negative result of at least one test (value lower than the
set minimum limit threshold).
M
15/10 – 18:04
RL-N
>
999 M
Vt
=
523 V
RL-PE = 250 M
Vt = 525 V
RN-PE > 999 M
Vt = 524 V
OK
AUTO 500V 1.00M
MODE
Vtest Lim.
3. Press the
SAVE
key to store the test result in the instrument’s memory (see § 7.1) or
the
ESC/MENU
key to exit the screen without saving and go back to the main
measuring screen.