EASYTEST-COMBI519
EN - 67
6.7.8. Verification of protection against indirect contacts (IT systems)
1. Press the
MENU
key, move the cursor to
LOOP
in the
main menu by means of the arrow keys (
,
) and
confirm with
ENTER
. Subsequently, the instrument
displays a screen similar to the one reported here to the
side.
Select “Europe” as a country (see § 5.1.2), the options
“IT”, “25 or 50V”, “50Hz or 60Hz” and the reference
voltage in the general settings of the instrument (see §
5.1.3).
L O O P
15/10 – 18:04
IT
Ipfc
Ut
=
=
- - -
- - -
mA
V
FREQ. = 0.00Hz
VL-PE=0V
VL-N=0V
L-PE Ut
FUNC
MODE
2. Use the
,
keys to select the parameter to be modified, and the
,
keys to modify the
parameter value:
FUNC
the virtual key allows setting the measuring mode of the instrument, which
may be
L-PE
.
MODE
fixed Ut limit set by the user (see § 5.1.2).
3. If possible, disconnect all loads connected downstream of the point to be measured, as
the impedance of these users could distort the test results. Perform the preliminary
calibration of the test leads as described in § 6.7.2.
4. Insert the green, blue and black connectors of the three-pin plug cable into the
corresponding inputs B3, B4 and B1 of the instrument. As an alternative, use the single
cables and apply the relevant alligator clips to the free ends of the cables. It is also
possible to use the remote switch probe by inserting its multipolar connector into the
input B1. Connect the mains plug, the alligator clips or the remote switch probe to the
electrical mains according to Fig. 27.
5. Note the correct voltage values between L-N and L-PE as
shown in the screen to the side.
L O O P
15/10 – 18:04
IT
Ipfc
Ut
=
=
- - -
- - -
mA
V
FREQ. = 50.00Hz
VL-PE=232V
VL-N=234V
L-PE Ut
FUNC
MODE
6. Press the
GO/STOP
key on the instrument, the
START
key on the remote switch probe or use the AutoStart
feature (see § 5.1.5). The instrument starts the
measurement and the “
Measuring…
” message is shown
on the display. During this whole stage, do not disconnect
the measuring leads of the instrument from the system
under test. The following screen appears on the
instrument's display.
L O O P
15/10 – 18:04
IT
Ipfc
Ut
=
=
- - -
- - -
mA
V
FREQ. = 50.00Hz
VL-PE=232V
VL-N=234V
Measuring…
L-PE Ut
FUNC
MODE