EASYTEST-COMBI519
EN - 94
10.2. REFERENCE GUIDELINES
Safety: IEC/EN61010-1,IEC/EN61010-2-030,IEC/EN61010-2-033
EMC: IEC/EN61010-2-034, IEC/EN61557-1
Technical documentation:
IEC/EN61187
Safety of accessories:
IEC/EN61010-031
Insulation:
double insulation
Pollution level:
2
Max. operating altitude:
2000m (6562ft)
Measurement category:
CAT IV 300V to earth, maximum 415V between inputs
RPE: IEC/EN61557-4,BS7671
17th/18th ed., AS/NZS3000/3017
M
:
IEC/EN61557-2,BS7671 17th/18th ed., AS/NZS3000/3017
RCD:
IEC/EN61557-6 (only on Phase-Neutral-Earth systems)
LOOP P-P, P-N, P-PE:
IEC/EN61557-3,BS7671 17th/18th ed., AS/NZS3000/3017
Multifunction: IEC/EN61557-10,BS7671
17th/18thed., AS/NZS3000/3017
Short-circuit current:
EN60909-0
10.3. GENERAL CHARACTERISTICS
Mechanical characteristics
Dimensions (L x W x H):
225 x 165 x 75mm ; (9 x 6 x 3in)
Weight (batteries included):
1.2kg ; (42 ounces)
Mechanical protection:
IP40
Power supply
Battery type:
6x1.5V alkaline batteries type AA IEC LR06 MN1500 or
6 x1.2V rechargeable NiMH type AA
Low battery indication:
low battery symbol “ ” on the display
Battery life:
> 500 tests for each function
Auto Power OFF:
after 5 minutes’ idling (if activated)
Miscellaneous
Display:
COG Black/white graphic LCD, 320x240pxl
10.4. ENVIRONMENT
10.4.1. Environmental conditions for use
Reference temperature:
23°C ± 5°C ; (73°F ± 41°F)
Operating temperature:
0°C ÷ 40°C ; (32°F ÷ 104°F)
Allowable relative humidity:
<80%RH
Storage temperature:
-10°C ÷ 60°C ; (14°F ÷ 140°F)
Storage humidity:
<80%RH
This instrument satisfies the requirements of Low Voltage Directive 2014/35/EU
(LVD) and of EMC Directive 2014/35/EU
This instrument satisfies the requirements of European Directive 2011/65/EU (RoHS)
and 2012/19/EU (WEEE)
10.5. ACCESSORIES
See enclosed packing list