August-2015
Page 4
1.
Introduction
HST-HP201-2 is an addressable fire alarm control panel capable to connect up to 250
HST addressable devices per loop. With its extra large graphical display, it configures almost
all panel settings via its very simple interface or with it’s built in PC interface via HST
RINGER configuration software. It stores almost all different actions monitored up to 4000
event log records.
HST-HP201-2 covers all small to medium size fire detection system needs.
2.
Features & specifications
2 onboard detection loops with maximum 250 devices per loop (HST protocol).
2 onboard programmable monitored conventional sounder lines.
3 onboard programmable relays.
3 onboard programmable dry contact inputs.
1 onboard free 24 voltage output.
4 onboard fixed alarm functional keys (silence buzzer, silence alarm, resound alarm,
reset).
1 onboard fixed evacuate key.
2 onboard programmable keys.
Full navigation keys & full numeric keypad.
16 onboard functional LED indicators for different panel states.
250 zones with 32 onboard zonal LED indicators.
4000 event log records.
Large graphical display (240 X 128 pixels).
1 RS-232 interface for PC panel con_guration tool.
Lock key for con_guration update access.
Real time clock.
Main supply input voltage: 230VAC 50Hz.
Main supply output voltage: 27VDC.
Main supply output current: 6.5A max.
Panel main fuse current: 5A.
Battery type: 2 X 12V 7Ah sealed lead acid.
Battery charging voltage: 27VDC.
Battery charging current: 700mA.
Free volatge output: 24V, 800 mA self ressetable fuse.
Sounder lines: 24V, 800 mA self ressetable fuse.
Sounder lines end of line resistance: 10KΩ.
Detection loop current: 190mA max(250 loop devices connected).
Loop protocol: HST.
Display: graphical LCD 240X128 pixels.
Computer interface: RS232.
Weight: ~ 4Kg(without batteries).
Dimensions: 450X370X120 mm.