HRW TLC-FCR-T Скачать руководство пользователя страница 7

 

 

TLC-FCR-T Operation 

 

 

Setting of parameters 

The TLC-FCR-T is an intelligent controller and can be adapted to fit perfect into your fan coil application. The control 
operation is defined by parameters. The parameters are set during operation by using the standard operation terminal.  
The parameters may only be accessed by entering a code. There are two levels of parameters: User operation 
parameters for access control settings and Expert parameters for control functions and unit setup. The codes for user 
levels and expert levels are different. Only control experts should be given the control parameter code.  
The parameters can be changed as follows: 

1.

 

Press UP and DOWN button simultaneously for three seconds. The display shows the software version in the 

large digits and the product code in the small digits.  

2.

 

Pressing any button will indicate CODE on the large digits and 000 on the small digits. 

3.

 

The code for accessing the user parameters is 009 

4.

 

Select this using UP or DOWN buttons. 

5.

 

Press OPTION button after selecting the correct code.  

6.

 

Once logged in, the parameter is displayed immediately. 

7.

 

Select the parameters with the UP/DOWN buttons. Change a parameter by pressing the OPTION button. The 

MIN and MAX symbols show up and indicate that the parameter may be modified now. Use UP or DOWN 
buttons to adjust the value. 

8.

 

After you are done, press OPTION or POWER in order to return to the parameter selection level.  

9.

 

Press the POWER button again so as to leave the menu. The unit will return to normal operation if no button 

is pressed for more than 5 minutes. 

User Parameters 

Parameter Description 

Setting 

Range Factory 

Setting 

UP 00 

Enable change of operation modes  

ON, OFF 

ON 

UP 01 

Enable change of set points 

ON, OFF 

ON 

UP 02 

Enable manual control of fan speeds 

ON, OFF 

ON 

UP 03 

Enable change of heating/cooling mode 

ON, OFF 

ON 

UP 04 

Enable access to Time programs 

ON, OFF 

ON 

UP 05 

State after power failure:  
0 = Switched OFF, 1 = Switched ON, 2 = state before power failure 

0, 1, 2 

UP 06 

Enable standby functionality 

ON, OFF 

ON 

UP 07 

Celsius or Fahrenheit, Select ON for Fahrenheit, OFF for Celsius 

ON, OFF 

OFF (Celsius) 

UP 08 

Calibration value of temperature sensor. This value is calibrated at 
manufacturing of the thermostat. If required it is possible to shift 
the temperature –10° to +10° in 0.1° K steps.  

-10…10 0 

UP 09 

Enable frost protection 

ON, OFF 

ON 

UP 10 

Select contents of Large LCD display in standard mode: 

00 = OFF 
01 = Setpoint 
02 = Temperature Input of control loop  
03 = Output Fan Speed 
04 = Clock 
05 = Alternate Temperature Sensor  

0…5 02 

 

Temperature 

UP 11 

Select contents of small LCD display in standard mode 
(use table of UP 10) 

0…5 04 

Deluxe 

01 Standard 

 
 

TLC-FCR-T, V2.0 22.03.2007                  HRW Limited              Subject to alteration Without Notice 

Page 7 

Содержание TLC-FCR-T

Страница 1: ...for a spring return valve General Description The TLC FCR T is a stand alone electronic fan coil controller with one control loop The TLC FCR T features 1 internal NTC temperature sensor one open contact or external NTC temperature input and four binary outputs Relays A detailed parameterization is possible with the use of a simple configuration routine The TLC FCR T can be configured using the st...

Страница 2: ... of fire proof ABS plastic 3 The front part made of white fire proof ABS plastic Installation 1 Arrange the wires to be connected and cut them to equal length 2 Connect them to the terminals of the power case according to wiring diagram 3 Clip the power case to the mounting plate pull the connection cable through the large central opening of the mounting plate Insert the power case into the flush ...

Страница 3: ... 6 N 230V AC L1 230V AC N DO1 DO2 DO3 DO4 Fan Low Fan Medium Fan High Valve H C 7 8 RT1 RT2 RTEXT OC RTEXT OC 1 0V AC 2 220V AC 3 Low 4 Med 5 High 6 Valve Attention Switching power is limited to 250VAC 300W 7 RT OC 8 RT OC 7 8 220V AC L 0V AC N 2 1 FAN 1 3 3 4 5 6 Valve RTEXT 7 8 43 1 7 88 3 5 21 0 8 30 1 2 30 1 2 88 3 5 Distance for mounting screws Horizontal and vertical 45 to 63mm 1 8 to 2 5 in...

Страница 4: ...FF based on weekdays and time may be programmed See chapter operation on how to program switch times A blinking clock indicates that the time needs to be set Time programs will not operate if the time is not defined See chapter operation advanced settings for instructions on how to set the time Occupation Sensor External Heat Cool change Auto change over Remotely control comfort and standby mode f...

Страница 5: ...ange Clock setup Time schedule The menu may be left by pressing the POWER button or by not pressing a button for more than 5 minutes Heat Cool Fan only change Pressing the OPTION button toggles Heating Cooling Fan only mode Access to Heat Cool change may be disabled with UP 03 Clock Setup and Time Schedule only available on Deluxe versions Clock Setup The current time is displayed in the small dig...

Страница 6: ...emperature loop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be activated in FAN ONLY mode Boost Pressing the boost button activates a 5 minute boost The output will be fully opened for the period of 5 minutes independent of demand This may be used to ...

Страница 7: ...may be modified now Use UP or DOWN buttons to adjust the value 8 After you are done press OPTION or POWER in order to return to the parameter selection level 9 Press the POWER button again so as to leave the menu The unit will return to normal operation if no button is pressed for more than 5 minutes User Parameters Parameter Description Setting Range Factory Setting UP 00 Enable change of operati...

Страница 8: ...lay OFF Prevents a too short running cycle for the heating or cooling stage by setting a minimum running time Delay OFF applies to all heating and cooling stages Delay ON Prevents a too short stopping cycle for heating or cooling stage by setting a minimum stopping time Delay ON applies to all heating and cooling stages Step by step switching In order to reduce the startup load of large fan motors...

Страница 9: ... and functionality of controller depend on its firmware revision It is therefore important to use a matching product version and parameter set The firmware version is shown on the large LCD digits when pressing UP and DOWN buttons for more than 3 seconds simultaneously Control Parameters Access Code 241 Warning Only experts should change these settings See user parameters for login procedure Param...