TLC-FCR-T Operation
Setting of parameters
The TLC-FCR-T is an intelligent controller and can be adapted to fit perfect into your fan coil application. The control
operation is defined by parameters. The parameters are set during operation by using the standard operation terminal.
The parameters may only be accessed by entering a code. There are two levels of parameters: User operation
parameters for access control settings and Expert parameters for control functions and unit setup. The codes for user
levels and expert levels are different. Only control experts should be given the control parameter code.
The parameters can be changed as follows:
1.
Press UP and DOWN button simultaneously for three seconds. The display shows the software version in the
large digits and the product code in the small digits.
2.
Pressing any button will indicate CODE on the large digits and 000 on the small digits.
3.
The code for accessing the user parameters is 009
4.
Select this using UP or DOWN buttons.
5.
Press OPTION button after selecting the correct code.
6.
Once logged in, the parameter is displayed immediately.
7.
Select the parameters with the UP/DOWN buttons. Change a parameter by pressing the OPTION button. The
MIN and MAX symbols show up and indicate that the parameter may be modified now. Use UP or DOWN
buttons to adjust the value.
8.
After you are done, press OPTION or POWER in order to return to the parameter selection level.
9.
Press the POWER button again so as to leave the menu. The unit will return to normal operation if no button
is pressed for more than 5 minutes.
User Parameters
Parameter Description
Setting
Range Factory
Setting
UP 00
Enable change of operation modes
ON, OFF
ON
UP 01
Enable change of set points
ON, OFF
ON
UP 02
Enable manual control of fan speeds
ON, OFF
ON
UP 03
Enable change of heating/cooling mode
ON, OFF
ON
UP 04
Enable access to Time programs
ON, OFF
ON
UP 05
State after power failure:
0 = Switched OFF, 1 = Switched ON, 2 = state before power failure
0, 1, 2
2
UP 06
Enable standby functionality
ON, OFF
ON
UP 07
Celsius or Fahrenheit, Select ON for Fahrenheit, OFF for Celsius
ON, OFF
OFF (Celsius)
UP 08
Calibration value of temperature sensor. This value is calibrated at
manufacturing of the thermostat. If required it is possible to shift
the temperature –10° to +10° in 0.1° K steps.
-10…10 0
UP 09
Enable frost protection
ON, OFF
ON
UP 10
Select contents of Large LCD display in standard mode:
00 = OFF
01 = Setpoint
02 = Temperature Input of control loop
03 = Output Fan Speed
04 = Clock
05 = Alternate Temperature Sensor
0…5 02
Temperature
UP 11
Select contents of small LCD display in standard mode
(use table of UP 10)
0…5 04
Deluxe
01 Standard