TLC-FCR-T Operation 

 

 
Err1:
 

Temperature sensor faulty. The connection to the temperature sensor may be interrupted or the temperature 
sensor is damaged. As a consequence all the outputs tied to this sensor are switched off. 

Operation of the Terminal Unit 

Switching ON 
The unit is switched on by pressing the POWER button. It will start up in comfort mode. 

Changing between COMFORT and STANDBY 
Pressing the POWER button for less than 2 seconds toggles between STANDBY and COMFORT modes. Standby mode 
may be disabled with UP06.  

Switching OFF 
Pressing the POWER button for more than 2 seconds, will switch the unit off. OFF and current time will be displayed in 
the LCD.  

Standard display 
This display mode is active if no UP/DOWN or OPTION button has been pressed during the previous 30 seconds.  The 
contents of the large and small digits may be chosen with parameters UP-10 and UP-11.  
Pressing UP/DOWN button will show the temperature setpoint in the small digits and room temperature in the large 
digits.  

Changing of set points 
Press UP/DOWN buttons to change temperature setpoint. Changing of set points may be disabled with UP-01. 

Fan speed override 
Manually change fan speeds by pressing the OPTION button for less than 3 seconds. Repeatedly pressing the OPTION 
button will toggle through these fan speed selections: Fan LOW 

 Fan MEDIUM 

 FAN HIGH 

 FAN Auto.  Any 

selection other than FAN Auto will display the manual override sign. Manual override of fan speeds may be disabled 
with UP-02 

Accessing advanced settings 

Pressing the option button for more than three seconds will start the advanced setup menu. The basic version will only 
show heat/cool setup. The deluxe version will allow access to the time setting function. 
The large LCD digits display SEL. The advanced setup menu accesses these settings: Heat / Cool change, Clock setup, 
Time schedule. The menu may be left by pressing the POWER button or by not pressing a button for more than 5 
minutes.  

 

Heat / Cool / Fan only change. Pressing the OPTION button toggles Heating – Cooling – Fan only mode.  
Access to Heat/Cool change may be disabled with UP-03 

Clock Setup and Time Schedule (only available on Deluxe versions) 

 

Clock Setup. The current time is displayed in the small digits. Pressing the OPTION button will enter the clock 
setup. The minutes are blinking and may be changed with the UP/DOWN buttons. Pressing OPTION saves the 
minutes and steps to the hours. The hours are blinking. Pressing the OPTION button again will step to the 
weekday. DAY1-7 is displayed. Day 1 stands for the first working day (Monday) of a 5-day working week. 
(See schedule). Select the day according to current weekday. Pressing Option again saves the settings and 
moves back to the SELECT menu.  

 

Time Schedules: press the option button while Pro is displayed in the small digits. Pro1 is now shown in the 
large digits, while the number 1 is blinking. Select time program by using UP/DOWN buttons. There are a 
total of 4 time programs with each 4 switching times available. Enter the time program by pressing the 
OPTION button. 
1.

 

Activate or deactivate the time program. Choose ON or OFF with the UP/DOWN buttons 

2.

 

Select weekday(s) = d1-7, d1-5, d6-7, day1, day2, day3, day4, day5, day6, day7 

The next steps define the switching mode and time. The bar indicator on the right side shows programming 
progress. There are four switch times for each program.  
3.

 

Select desired operation mode. (no, ON, Eco, OFF), press OPTION to continue 

ƒ

 

no = disables this switching time 

ƒ

 

On = sets operation mode to On and Comfort 

ƒ

 

Eco = sets operation mode to On and Standby 

ƒ

 

OFF = switches unit Off 

4.

 

Select switching time 00:00 to 23:45 in 15-minute steps; press OPTION to continue. 

5.

 

Repeat steps 3 and 4 for each switching time.  

Access to time schedules may be disabled with UP-04 

TLC-FCR-T, V2.0 22.03.2007                  HRW Limited              Subject to alteration Without Notice 

Page 5 

Содержание TLC-FCR-T

Страница 1: ...for a spring return valve General Description The TLC FCR T is a stand alone electronic fan coil controller with one control loop The TLC FCR T features 1 internal NTC temperature sensor one open contact or external NTC temperature input and four binary outputs Relays A detailed parameterization is possible with the use of a simple configuration routine The TLC FCR T can be configured using the st...

Страница 2: ... of fire proof ABS plastic 3 The front part made of white fire proof ABS plastic Installation 1 Arrange the wires to be connected and cut them to equal length 2 Connect them to the terminals of the power case according to wiring diagram 3 Clip the power case to the mounting plate pull the connection cable through the large central opening of the mounting plate Insert the power case into the flush ...

Страница 3: ... 6 N 230V AC L1 230V AC N DO1 DO2 DO3 DO4 Fan Low Fan Medium Fan High Valve H C 7 8 RT1 RT2 RTEXT OC RTEXT OC 1 0V AC 2 220V AC 3 Low 4 Med 5 High 6 Valve Attention Switching power is limited to 250VAC 300W 7 RT OC 8 RT OC 7 8 220V AC L 0V AC N 2 1 FAN 1 3 3 4 5 6 Valve RTEXT 7 8 43 1 7 88 3 5 21 0 8 30 1 2 30 1 2 88 3 5 Distance for mounting screws Horizontal and vertical 45 to 63mm 1 8 to 2 5 in...

Страница 4: ...FF based on weekdays and time may be programmed See chapter operation on how to program switch times A blinking clock indicates that the time needs to be set Time programs will not operate if the time is not defined See chapter operation advanced settings for instructions on how to set the time Occupation Sensor External Heat Cool change Auto change over Remotely control comfort and standby mode f...

Страница 5: ...ange Clock setup Time schedule The menu may be left by pressing the POWER button or by not pressing a button for more than 5 minutes Heat Cool Fan only change Pressing the OPTION button toggles Heating Cooling Fan only mode Access to Heat Cool change may be disabled with UP 03 Clock Setup and Time Schedule only available on Deluxe versions Clock Setup The current time is displayed in the small dig...

Страница 6: ...emperature loop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be activated in FAN ONLY mode Boost Pressing the boost button activates a 5 minute boost The output will be fully opened for the period of 5 minutes independent of demand This may be used to ...

Страница 7: ...may be modified now Use UP or DOWN buttons to adjust the value 8 After you are done press OPTION or POWER in order to return to the parameter selection level 9 Press the POWER button again so as to leave the menu The unit will return to normal operation if no button is pressed for more than 5 minutes User Parameters Parameter Description Setting Range Factory Setting UP 00 Enable change of operati...

Страница 8: ...lay OFF Prevents a too short running cycle for the heating or cooling stage by setting a minimum running time Delay OFF applies to all heating and cooling stages Delay ON Prevents a too short stopping cycle for heating or cooling stage by setting a minimum stopping time Delay ON applies to all heating and cooling stages Step by step switching In order to reduce the startup load of large fan motors...

Страница 9: ... and functionality of controller depend on its firmware revision It is therefore important to use a matching product version and parameter set The firmware version is shown on the large LCD digits when pressing UP and DOWN buttons for more than 3 seconds simultaneously Control Parameters Access Code 241 Warning Only experts should change these settings See user parameters for login procedure Param...