HRW TLC-FCR-T Скачать руководство пользователя страница 2

 

 

TLC-FCR-T Introduction

 

 

Technical Specification 

Power Supply 

Operating Voltage 

210 – 240 V AC 50/60 Hz 

 

Power Consumption 

Max 1W, 1.5 VA 

 

Electrical Connection 

Terminal Connectors 

Signal Inputs 

Temperature Inputs 

Range 
Resolution 
Accuracy 

RT Internal, External (Sxx-Tn10 sensor) 

-40°C…70°C (-40°F to 158°F) 
0.1°C (0.1°F) 
0.5°C (1°F) 

Signal Outputs 

Digital Switching Outputs 

Switching type 
AC Switching power 

DO1…DO4 
Relays 
2(1.2) A, 250VAC (max fan power 300W) 

Environment Operation 

Climatic Conditions 
Temperature 
Humidity 

To IEC 721-3-3 
class 3 K5 
0°C …50°C (32°F…122°F) 
<95% R.H. non-condensing 

 

Transport & Storage 

Climatic Conditions 
Temperature 
Humidity 
Mechanical Conditions 

To IEC 721-3-2 and IEC 721-3-1 

class 3 K3 and class 1 K3 
-25°C…0°C (-13°F…158°F) 
<95% R.H. non-condensing 
class 2M2 

Standards 

 

conform according to  
EMC Standard 89/336/EEC 
EMEI Standard 73/23/EEC 

 
EN 61 000-6-1/ EN 61 000-6-3 

 

Product standards 

Automatic electrical controls for 
household and similar use 
Special requirement on 
temperature dependent controls 

 
EN 60 730 –1 
 
EN 60 730 – 2 - 9 

 

Degree of Protection 

IP30 to EN 60 529 

 

Safety Class 

I (IEC 60536) 

General 

Dimensions (H x W x D) 

Front part: 21 x 88 x 88mm (0.8 x 3.5 x 3.5 in.)  

Power case: 60 x 50 x 30mm (2.4 x 2.0 x 1.2 in.) 

 

Weight (including package) 

260g 

  
Mechanical Design and Installation 

The unit consists of three parts:  

1.

 

The mounting plate made of galvanized steel.  

2.

 

The power case made of fire proof ABS plastic.  

3.

 

The front part made of white fire proof ABS plastic.  

Installation 

1.

 

Arrange the wires to be connected and cut them to equal length.  

2.

 

Connect them to the terminals of the power case according to wiring diagram 

3.

 

Clip the power case to the mounting plate, pull the connection cable through the large central opening of the 

mounting plate. Insert the power case into the flush mounting box. Carefully arrange power wires.  

4.

 

Install the mounting plate to the flush mounting box. Make sure that the nipple with the front holding screw is 

facing to the ground. Make sure the screw heads do not stand out more than 5 mm of the surface of the 
mounting plate.  

5.

 

Connect the connection cable to the plug located on the back of the front part. 

6.

 

Slide the two latches located on the top of the front part into the hooks of the mounting plate.  

7.

 

Lower the front part until located flat on the wall and the mounting plate is not visible anymore. Make sure 

the connection cable does not get into the way. 

8.

 

Tighten the front holding screw to secure the front part to the mounting plate.  

Mounting location 

 

On an easy accessible interior wall, approx. 1.5 m above the floor in an area of average temperature. 

 

Avoid direct sunlight or other heat sources, e.g. the area above radiators and heat emitting electrical 
equipment.  

 

Avoid locations behind doors, outside walls and below or above air discharge grills and diffusers.  

 

Location of mounting is less critical if external temperature sensors are used. 

 

TLC-FCR-T, V2.0 22.03.2007                  HRW Limited              Subject to alteration Without Notice 

Page 2 

Содержание TLC-FCR-T

Страница 1: ...for a spring return valve General Description The TLC FCR T is a stand alone electronic fan coil controller with one control loop The TLC FCR T features 1 internal NTC temperature sensor one open contact or external NTC temperature input and four binary outputs Relays A detailed parameterization is possible with the use of a simple configuration routine The TLC FCR T can be configured using the st...

Страница 2: ... of fire proof ABS plastic 3 The front part made of white fire proof ABS plastic Installation 1 Arrange the wires to be connected and cut them to equal length 2 Connect them to the terminals of the power case according to wiring diagram 3 Clip the power case to the mounting plate pull the connection cable through the large central opening of the mounting plate Insert the power case into the flush ...

Страница 3: ... 6 N 230V AC L1 230V AC N DO1 DO2 DO3 DO4 Fan Low Fan Medium Fan High Valve H C 7 8 RT1 RT2 RTEXT OC RTEXT OC 1 0V AC 2 220V AC 3 Low 4 Med 5 High 6 Valve Attention Switching power is limited to 250VAC 300W 7 RT OC 8 RT OC 7 8 220V AC L 0V AC N 2 1 FAN 1 3 3 4 5 6 Valve RTEXT 7 8 43 1 7 88 3 5 21 0 8 30 1 2 30 1 2 88 3 5 Distance for mounting screws Horizontal and vertical 45 to 63mm 1 8 to 2 5 in...

Страница 4: ...FF based on weekdays and time may be programmed See chapter operation on how to program switch times A blinking clock indicates that the time needs to be set Time programs will not operate if the time is not defined See chapter operation advanced settings for instructions on how to set the time Occupation Sensor External Heat Cool change Auto change over Remotely control comfort and standby mode f...

Страница 5: ...ange Clock setup Time schedule The menu may be left by pressing the POWER button or by not pressing a button for more than 5 minutes Heat Cool Fan only change Pressing the OPTION button toggles Heating Cooling Fan only mode Access to Heat Cool change may be disabled with UP 03 Clock Setup and Time Schedule only available on Deluxe versions Clock Setup The current time is displayed in the small dig...

Страница 6: ...emperature loop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan speed will not be activated in FAN ONLY mode Boost Pressing the boost button activates a 5 minute boost The output will be fully opened for the period of 5 minutes independent of demand This may be used to ...

Страница 7: ...may be modified now Use UP or DOWN buttons to adjust the value 8 After you are done press OPTION or POWER in order to return to the parameter selection level 9 Press the POWER button again so as to leave the menu The unit will return to normal operation if no button is pressed for more than 5 minutes User Parameters Parameter Description Setting Range Factory Setting UP 00 Enable change of operati...

Страница 8: ...lay OFF Prevents a too short running cycle for the heating or cooling stage by setting a minimum running time Delay OFF applies to all heating and cooling stages Delay ON Prevents a too short stopping cycle for heating or cooling stage by setting a minimum stopping time Delay ON applies to all heating and cooling stages Step by step switching In order to reduce the startup load of large fan motors...

Страница 9: ... and functionality of controller depend on its firmware revision It is therefore important to use a matching product version and parameter set The firmware version is shown on the large LCD digits when pressing UP and DOWN buttons for more than 3 seconds simultaneously Control Parameters Access Code 241 Warning Only experts should change these settings See user parameters for login procedure Param...

Отзывы: