5. Technical Specifications 

Designation: 

HRT 6510-50 

 

Setting ranges: 

Room temperature controller: 

5 ... 30 °C 

Floor temperature controller:  

10 ... 40 °C 

Floor temperature monitoring: 

20 ... 40 °C 

Supplementary heating:  

10 ... 40 °C 

Cooling controller: 

5 ... 30 °C 

 

Specification: 

Multi-colour display 

Powerline: 

HomePlug module 

Mains voltage:  

230 V ~ ±10%, 50 Hz 

Switching current (max.), approx.:  

12 (4) A  

Switching power:   

2.7 kW 

Power consumption in  

standby mode: 

1.0 W 

 

Maximum number of group controller:  16 per group 

Switching temperature difference:  

0.7 K 

Temperature sensor:  

NTC acc. to DIN 44574, 4m long 

Permissible ambient temperature: 

-10 ... +40 °C 

Connection cables:  

2.5 mm² 

Degree of protection: 

IP30 

Energy class 

VII 

Contribution to energy efficiency: 

3.5% 

Housing dimensions: 

71 x 71 x 41 mm 

Frame dimensions: 

80 x 80 mm 

Colour: 

Alpine-white (similar to RAL 9010) 

Compatibility: 

50x50 mm, with intermediate frame  

Weight: 

84 g 

Weight of the floor sensor: 

140 g 

 

Default settings: 

Default display temperature: 

Room temperature 

Default controller: 

Floor temperature controller 

Default sensor type: 

HRT standard floor sensor 

Default room temperature offset:  

0.0 K 

Default floor temperature offset: 

0.0 K 

Teach-in function: 

Off 

Type of programming: 

Block programming 

Comfort times  

Mon - Fri 6:00 a.m. - 9:00 a.m. / 05.00 p.m. - 10:00 p.m. 

 

Sat - Son 6:00 a.m. - 9:00 a.m. / 05:00 p.m. - 10:00 p.m. 

First setback temperature: 

3 °C 

Second setback temperature: 

Off 

Switching output inverted: 

Off 

Cooling controller:  

Off 

Valve protection: 

Off 

Switching cycle: 

0 min. 

Supplementary heating:  

Off 

Switching power: 

0 kW 

Frost protection: 

5 °C 

Automatic timing 

On 

Automatic daylight time: 

On 

Network: 

Off 

HomePlug:  

Off 

Grouping: 

Off 

 

6. Troubleshooting 

Diagnosis 

 

 

Possible Cause / Remedy 

Heating does not work 

 

Connect / check mains voltage 

 

Display: 

- No display   

 

Mains power failure 

- Error 

 

 

System-relevant error (e.g. sensor breakage) 

- HomePlug   

 

Network not connected/does not exist 

- Probe error  

 

Probe not connected/defective - check 

- Window sensor 

 

Window sensor not connected/defective 

- Switches too early / too late 

Check settings in the program 

- No reaction when changing temp. 

Check setback mode 

- Network error 

 

See display for detailed error messages 

- System reset 

 

Simultaneously press keys 1, 2 and 4 for 10s.; 

 

 

 

all user data are retained 

 

 

Содержание ECOTIMER P

Страница 1: ...t with multi colour RGB LED backlit display Any colour can be selected in accordance with the customer s individual wishes The temperature controller is equipped with a current saving power supply unit which not only contributes to the saving of natural resources with 15 less energy consumption compared to conventional control units but thanks to lower energy consumption also helps to reduce your ...

Страница 2: ...red temperature Use the plus and minus keys to change the value use the back arrow to quit the menu If no inputs are made for 10s the display is reset to the default values To turn on the backlight press any key once Key lock Enable key lock Simultaneously press and hold down the keys 1 and 4 for 10s until the lock symbol is displayed Disable key lock Simultaneously press and hold down the keys 1 ...

Страница 3: ...setting Grouping New Group Add Group Comfort temperature times Programming of the comfort temperature times in block or single day mode Block mode Same time program for the workdays 1 to 5 1 Monday 2 Tuesday etc Weekend 6 Saturday 7 Sunday single day mode programming Daily changeable time program is selected in the SETUP menu Default settings Mon Fri Time 1 06 00 a m 09 00 a m Mon Fri Time 2 05 00...

Страница 4: ...re controller Default setting Floor temperature controller Room temperature controller sensor Room temperature controller open window sensor integrated shutdown all the other controllers via external pluggable connector After changing the controller mode it is imperative for safety reasons to set it to Frost protection check that the frost protection symbol is displayed check the comfort and setba...

Страница 5: ...ion MAC address number of total operating hours error messages factory default settings and the energy consumption Floor temperature display floor and room temperature controllers with temperature monitoring only Software version MAC address Operating hours Error messages Factory settings No Yes Default setting No Consumption Network Specify the network settings DHCP OFF ON Factory setting OFF IP ...

Страница 6: ...witch box It is connected as to be seen on the wiring diagram see illustration Make sure that the connection cables are straight their ends must be stripped by approx 5mm Installation height Approx 1 5m above the floor Attention Place the frame ring over the edges of the wallpaper Mount the controller on the mounting box by using thread forming tapping screws supplied with the box Then place the f...

Страница 7: ...ure controller Default sensor type HRT standard floor sensor Default room temperature offset 0 0 K Default floor temperature offset 0 0 K Teach in function Off Type of programming Block programming Comfort times Mon Fri 6 00 a m 9 00 a m 05 00 p m 10 00 p m Sat Son 6 00 a m 9 00 a m 05 00 p m 10 00 p m First setback temperature 3 C Second setback temperature Off Switching output inverted Off Cooli...

Страница 8: ...r than as intended are not covered by the liability for defects We do not assume liability arising from the consequences of improperly performed modifications or repair This also applies to the delivery of components and spare parts HRT does not assume liability for damage on the delivery item itself in particular not for indirect consequential damages or financial losses Disposal Disposal of elec...

Отзывы: