5. Technical Specifications
Designation:
HRT 6510-50
Setting ranges:
Room temperature controller:
5 ... 30 °C
Floor temperature controller:
10 ... 40 °C
Floor temperature monitoring:
20 ... 40 °C
Supplementary heating:
10 ... 40 °C
Cooling controller:
5 ... 30 °C
Specification:
Multi-colour display
Powerline:
HomePlug module
Mains voltage:
230 V ~ ±10%, 50 Hz
Switching current (max.), approx.:
12 (4) A
Switching power:
2.7 kW
Power consumption in
standby mode:
1.0 W
Maximum number of group controller: 16 per group
Switching temperature difference:
0.7 K
Temperature sensor:
NTC acc. to DIN 44574, 4m long
Permissible ambient temperature:
-10 ... +40 °C
Connection cables:
2.5 mm²
Degree of protection:
IP30
Energy class
VII
Contribution to energy efficiency:
3.5%
Housing dimensions:
71 x 71 x 41 mm
Frame dimensions:
80 x 80 mm
Colour:
Alpine-white (similar to RAL 9010)
Compatibility:
50x50 mm, with intermediate frame
Weight:
84 g
Weight of the floor sensor:
140 g
Default settings:
Default display temperature:
Room temperature
Default controller:
Floor temperature controller
Default sensor type:
HRT standard floor sensor
Default room temperature offset:
0.0 K
Default floor temperature offset:
0.0 K
Teach-in function:
Off
Type of programming:
Block programming
Comfort times
Mon - Fri 6:00 a.m. - 9:00 a.m. / 05.00 p.m. - 10:00 p.m.
Sat - Son 6:00 a.m. - 9:00 a.m. / 05:00 p.m. - 10:00 p.m.
First setback temperature:
3 °C
Second setback temperature:
Off
Switching output inverted:
Off
Cooling controller:
Off
Valve protection:
Off
Switching cycle:
0 min.
Supplementary heating:
Off
Switching power:
0 kW
Frost protection:
5 °C
Automatic timing
On
Automatic daylight time:
On
Network:
Off
HomePlug:
Off
Grouping:
Off
6. Troubleshooting
Diagnosis
Possible Cause / Remedy
Heating does not work
Connect / check mains voltage
Display:
- No display
Mains power failure
- Error
System-relevant error (e.g. sensor breakage)
- HomePlug
Network not connected/does not exist
- Probe error
Probe not connected/defective - check
- Window sensor
Window sensor not connected/defective
- Switches too early / too late
Check settings in the program
- No reaction when changing temp.
Check setback mode
- Network error
See display for detailed error messages
- System reset
Simultaneously press keys 1, 2 and 4 for 10s.;
all user data are retained