Select mode: 

  

 

To turn on the backlight, press any key once. 

To activate the "Mode" menu, press the MENU key. Use the arrow keys for mode selection. 

 

 

 

 

 

 

 

FROST PROTECTION 

MANUAL  

 

AUTOMATIC  

Press OK to confirm  

 
Main menu: 

  

 

Press and hold down the MENU key for 

3 sec.

; use the arrow keys for selection. 

 

 

Comfort temp. (is used to program the comfort temperature times) 

 

 

Temperatures (frost protection/setback temperature) 

 

 

Display (brightness, backlight, contrast, colour settings) 

 

 

Settings (date, time, daylight time, language, unit) 

 

 

Setup (controller and sensor probe mode, offset, teach-in function,  

 

program, setback temperature 2, switching output) 

 

 

Device info (software version, operating hours, 

 

error messages, factory settings) 

 

 

Network (DHCP, IP address, hostname, time server,  

 

time zone, user name, password

 

 

 

HomePlug (Add HomePlug, default setting) 

 

 

Grouping (New Group, Add Group) 

 

Comfort temperature times: 

 

 

Programming of the comfort temperature times in block or single day mode 

 

 

 

Block mode:   

        Same time program for the  

 

workdays 1 to 5  

        (1 = Monday, 2 = Tuesday, etc.)  

 

Weekend    

        (6 = Saturday, 7 = Sunday) 

 

single day mode programming: Daily changeable time program  

 

(is selected in the SETUP menu) 

 

 

 

Default settings: 

    

Mon - Fri 

Time 1 

06:00 a.m. -> 09:00 a.m. 

 

Mon - Fri 

Time 2 

05:00 p.m. -> 10:00 p.m. 

 

Sat - Son 

Time 1 

06:00 a.m. -> 09:00 a.m. 

 

Sat - Son 

Time 2 

05:00 p.m. -> 10:00 p.m. 

 

 

Outside the comfort temperature times, the setpoint temperature is reduced to the setback temperature. 

 

Temperatures: 

 

 

Display or change frost protection ranges/setback temperatures 

 

 

 

Frost protection 

Range: 3.0 ... 15.0 K 

 

Default setting: 5.0 K 

 

Setback temperature 1 

Range: 1.0 ... 15.0 K 

 

Default setting: 3.0 K 

 

Setback temperature 2 

Range: 1.0 ... 15.0 K 

 

Default setting: Nothing is displayed 

 

 

 

(is selected in the SETUP menu) 

 

Sensor temperature  

Range: 20.0 ... 40.0 K 

 

Default setting: 28.0 K 

 

 

 

(variant with temperature monitoring only) 

 

 

Содержание ECOTIMER P

Страница 1: ...t with multi colour RGB LED backlit display Any colour can be selected in accordance with the customer s individual wishes The temperature controller is equipped with a current saving power supply unit which not only contributes to the saving of natural resources with 15 less energy consumption compared to conventional control units but thanks to lower energy consumption also helps to reduce your ...

Страница 2: ...red temperature Use the plus and minus keys to change the value use the back arrow to quit the menu If no inputs are made for 10s the display is reset to the default values To turn on the backlight press any key once Key lock Enable key lock Simultaneously press and hold down the keys 1 and 4 for 10s until the lock symbol is displayed Disable key lock Simultaneously press and hold down the keys 1 ...

Страница 3: ...setting Grouping New Group Add Group Comfort temperature times Programming of the comfort temperature times in block or single day mode Block mode Same time program for the workdays 1 to 5 1 Monday 2 Tuesday etc Weekend 6 Saturday 7 Sunday single day mode programming Daily changeable time program is selected in the SETUP menu Default settings Mon Fri Time 1 06 00 a m 09 00 a m Mon Fri Time 2 05 00...

Страница 4: ...re controller Default setting Floor temperature controller Room temperature controller sensor Room temperature controller open window sensor integrated shutdown all the other controllers via external pluggable connector After changing the controller mode it is imperative for safety reasons to set it to Frost protection check that the frost protection symbol is displayed check the comfort and setba...

Страница 5: ...ion MAC address number of total operating hours error messages factory default settings and the energy consumption Floor temperature display floor and room temperature controllers with temperature monitoring only Software version MAC address Operating hours Error messages Factory settings No Yes Default setting No Consumption Network Specify the network settings DHCP OFF ON Factory setting OFF IP ...

Страница 6: ...witch box It is connected as to be seen on the wiring diagram see illustration Make sure that the connection cables are straight their ends must be stripped by approx 5mm Installation height Approx 1 5m above the floor Attention Place the frame ring over the edges of the wallpaper Mount the controller on the mounting box by using thread forming tapping screws supplied with the box Then place the f...

Страница 7: ...ure controller Default sensor type HRT standard floor sensor Default room temperature offset 0 0 K Default floor temperature offset 0 0 K Teach in function Off Type of programming Block programming Comfort times Mon Fri 6 00 a m 9 00 a m 05 00 p m 10 00 p m Sat Son 6 00 a m 9 00 a m 05 00 p m 10 00 p m First setback temperature 3 C Second setback temperature Off Switching output inverted Off Cooli...

Страница 8: ...r than as intended are not covered by the liability for defects We do not assume liability arising from the consequences of improperly performed modifications or repair This also applies to the delivery of components and spare parts HRT does not assume liability for damage on the delivery item itself in particular not for indirect consequential damages or financial losses Disposal Disposal of elec...

Отзывы: