Display:
Display and change brightness, backlight, contrast, and colour settings
Brightness
Range: 0 ... 100%
Default setting: 75%
Backlight time
Range: 10 ... 60 s
Default setting: 30 s
Contrast
Range: 0 ... 100%
Default setting: 50%
Red
Range: 0 ... 100%
Default setting: 25%
Green
Range: 0 ... 100%
Default setting: 55%
Blue
Range: 0 ... 100%
Default setting: 40%
Colour legend:
(RGB colour = Red/green/blue) Specified in percent
Display-settings:
Display or change automatic timing, daylight time, language, unit, floor temperature
Automatic timing
ON / OFF
Default setting: ON
OFF
→
Set date/time manually
Daylight time
OFF / ON
Default setting: ON
OFF
→
Set time manually
Language
German, English, and others
Default setting: German
Unit
Celsius / Fahrenheit
Default setting: Celsius
Floor temperature
OFF / ON
ON
→
The floor temperature is displayed.
(and, in addition, the floor temperature symbol)
OFF
→
The room temperature is displayed.
Default setting: OFF
SETUP:
Display and change controller mode, sensor probe mode, offset settings, teach-in function, program,
setback temperature 2, switching output, cooling controller, valve protection, switching cycle,
supplementary heating, switching power
Any changes in the SETUP menu can lead to uncontrolled functions and should therefore
only be performed by authorised electrical experts.
Controller mode
Select
Room temperature controller
Floor temperature controller
Default setting: Floor temperature
controller
Room temperature cont sensor
Room temperature cont open window sensor (integrated shutdown;
all the other controllers via external pluggable connector)
After changing the controller mode, it is imperative for safety reasons to set it to "Frost protection"
(check that the frost protection symbol is displayed); check the comfort and setback temperatures.
Sensor type selection
HRT sensor
Default setting: Sensor
10 k
Ω
NTC, e.g. Busch-Jaeger
12 k
Ω
NTC, e.g. OJ
15 k
Ω
NTC, e.g. DEVI
33 k
Ω
NTC, e.g. Eberle
2 K
Ω
PTC
Room temperature offset Measurement correction for the room temperature display
Range: - 3.0 K ... 3.0 K
Default setting: 0.00 °C
Floor temperature offset Measurement correction for the floor temperature display
Range: - 3.0 K ... 3.0 K
Default setting: 0.00 °C
(floor and room temperature controllers with temperature monitoring only)
Teach-in function
Autonomous determination of the preheating time to be able to
reach the selected comfort temperature
OFF / ON
Default setting: OFF
Program
Select block program or single day mode program
Default setting: Block program
Setback temperature 2
Allows you to select a different setback temperature between the
end of the comfort time 1 and the beginning of the comfort time 2
OFF / ON
Default setting: OFF
Colour
Red Green Blue
Colour
Red Green Blue
Red
100
0
0
Orange 100
65
0
Green
0
100
0
Yellow
100
100
0
Blue
0
0
100
Green
0
50
0
Fuchsia 100
0
100
Olive
50
50
0
Purple
100
73
100
Maroon
50
0
0
White
100
100
100
Navy
0
0
50