HRS Hevac Ltd AquaSave A6 Range
Installation, Operating & Instruction Manual
9.6 Safety
Function
This function activates all the pumps' power relays at the same time without considering ipsothermic contacts'
inputs.
NOTE:
This function can be enabled from end user level.
In case of high temperature alarm on S1, the primary pumps are stopped, even if the function is
activated.
9.7 Eco-Booster
Function
ECO
: When control valve is sufficiently closed (Valve Hysteresis) during a sufficient long time (ECO
delay), primary pump switches off and primary mixing valve close down.
The system is switch ON when S1 temperature has gone down more than the set value of
”Eco Hysteresis”.
If secondary pumps are connected (SS/DS/DD series) they are still in operation during the Eco
function.
Booster
function is not available in AquaCompact
Parameter
Factory Setting
Optional setting
Description
0:-
1:E
2:B
3:E+B
0
0/1/
0 = No function
1 = Eco Function only
2 = N/A
3 = N/A
Fct_Selection
Normal
Normal/Eco/Boost/
EcoBoost
Playback function selected in
1:Eco 2:Booster 3:ECoBoost
Eco Delay
5 min
1-30 min
Scan time before activating function if
possible
Eco Hysteresis
5°C
1-20°C
Temperature range in which the function is
applicable
Valve Hysteresis.
10%
0-80%
Maximum opening of the valve before
switching function
Booster Delay
2 sec
2-200 sec
Time delay between the Booster functions
stops and the second pump stops (N/A)
Booster Gradient
2°K/s
1 to 20°K/sec
Minimum temperature fall speed at which
the function operates (N/A)
Parameter
Factory Setting
Optional Setting
SAFETY_Speed
75%
Not used
SAFETY FCT
Off
Off/On