HRS Hevac Ltd AquaSave A6 Range
Installation, Operating & Instruction Manual
Setting the DHW flow rate
4
The secondary DHW flow rate is set with the tank full and the primary circuit at nominal operating temperature
and at the available exchanger power capacity required for the generator.
1. Fully open up the control valve on the primary side.
2. If a 3-way control valve is fitted, wait for it to open completely.
3. Adjust the secondary flow circuit, as set out in the table below.
The flow rate can be read by pressing on the red pushbutton and reading the index marker against the
float.
Flow controller
Read-off index marker
Read-off pushbutton
P(kW)
DHW T(°C)
30 40 50 60 70 80 90 100
125
150
175
200
240
10
>
55°C 9.5 13 16 19 22 25.5
28.5
32 40 48 56 63 76
10
>
60°C 8.5 11.5
14 17 20 23 26 28 35 43 50 57 68
5
>
70°C
6 9 11 13 15 17 20 22 27 33 38 44 53
The recirculation flow rate has to be 60% maximum of the secondary flow rate.