![HRS AQUASAVE A6 Series Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/hrs/aquasave-a6-series/aquasave-a6-series_operating-instructions-manual_2177342019.webp)
t.
01923 232335
www.hrshevac.co.uk
19 of 58
HRS Hevac Ltd AquaSave A6 Range
Installation, Operating & Instruction Manual
End user mode
8
The following changes can be done in end user mode:
Settings which are identical/different for each day of the week at defined times
Normal temperature(s)
Lower temperature(s)
Special period of defined duration during the current year
Waiver with change of setting at a specific time.
One time temperature change at a specific time.
8.1
Set the hot water temperature
Please set a hot water production temperature in line with current national legislation and recommendations
(UTD, Standards EN, ISO etc.)
All countries have different rules for how hot or cold tap water should be.
HRS Hevac recommends the hot water temperature is at least 55°C
and a hot water recirculation not less than
50°C.
At a temperature below 50°C there is a risk of bacterial growth.
Note that at temperatures above 60°C the risk of scalding increases.
Set points above 63°C result in an increased risk of precipitation of lime scaling on the surfaces of the heat
exchanger.
8.2
Time programs
The time programs used in AquaSave are adjusted the same way.
Time programs:
SP_T_Sec_Outlet, to be found in the menu
9.4 S1 Menu Secondary Outlet
. It is to set the DHW
temperature
ThTr_Activated to be found in
9.5 Thermal Treatment Menu
, to activate a thermal treatment (1 sensor
mode).
Multi_P to be found in
9.9 230V Triac menu
, to activate the 230V power output on the controller
The time program has two different temperature modes - week program or weekend-program.
For each day of the week, define which time program to use.
By default has the weekend-program the same settings as the week- program.
It is even possible to customize the temperature programs with special dates (holidays periods or free days).
Each time program can have a number of different times set per day, each time can have a different
temperature. The set temperature is then in effect until the next time occurs. If only one temperature is set, the
program will run with the set temperature.