Chapter 5 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
―
56
―
HD3N-TC Series Inverter User Manual V1.0
Ref. code
Name Description
Setting Range [Default]
F19.19
Stall overvoltage point
220V inverter:
350 - 400 [380V]
380V inverter:
650 - 790 [690V]
If overvoltage occurs during running, properly
increase stall overvoltage gain and decrease F19.19.
Stall overvoltage and braking unit:
•
Usually when applying braking units to inverter,
please forbid stall overvoltage (F19.18 = 0);
•
But if feedback energy is too large at loading
moment and delayed energy release of braking
unit, inverter will adopt overvoltage protection. To
avoid protection, enable stall overvoltage and
F19.19 should > action voltage of braking unit.
△
F = F19.18 × (V
DC
- F19.19)
Auto current limit (F19.20 - F19.21)
Auto current limit is used to limit the load current in real time < F19.21. Therefore inverter will not
trip due to surge current. It is especially suitable for applications with big load inertia or big change
of load.
In auto current limit process, output frequency of inverter may change; therefore, it is recommended
not to enable when stable output frequency is required.
Ref. code
Name Description
Setting Range [Default]
F19.20
Auto current limit gain
0.000 - 1.000 [0.200]
Output frequency of inverter > F19.21, inverter will limit current to avoid over-current protection.
•
Adjust F19.20 according to actual load:
•
If F19.20 is too small, it can not fully limit increase of output current;
•
If F19.20 is too large, output frequency will fluctuate even system oscillates.
•
Auto current limt is invalid when F19.20 = 0.
F19.21
Auto current limit threshold
20.0 - 200.0 [150.0%]
Defines the current threshold of auto current limit. The current = F19.21 × rated current of inverter.
•
When auto current limit is valid, if F19.21 is too small, it may affect the load capacity of inverter.
Terminal detection (F19.23)
Ref. code
Name Description
Setting Range [Default]
F19.23
Terminal running command detection
0,1 [0]
0: Edge is valid.
1: Level is valid.
Busbar voltage
F19.19
Setting frequency
Reference
frequency
Time
Time
Voltage
Frequency
Содержание HD3N-2D0P7G-TC