Chapter 5 Function Introduction
Shenzhen Hpmont Technology Co., Ltd.
―
48
―
HD3N-TC Series Inverter User Manual V1.0
Ref. code
Name Description
Setting Range [Default]
123
K3 (No. 15)
K2 (No. 14)
K1 (No. 13)
Frequency setting
0 0 0
Not
change
0
0
1
Multi frequency 1 (F06.00)
0
1
0
Multi frequency 2 (F06.01)
0
1
1
Multi frequency 3 (F06.02)
1
0
0
Multi frequency 4 (F06.03)
1
0
1
Multi frequency 5 (F06.04)
1
1
0
Multi frequency 6 (F06.05)
1
1
1
Multi frequency 7 (F06.06)
17,18: Increase (UP) / decrease (DN) frequency.
•
Increase or decrease frequency by terminal, equal to remote control by keypad.
•
Range is set by F15.12. Refer to below table.
•
Valid when F00.10 = 1 (digital setting).
UP (No. 17)
DN (No. 18)
Frequency change
0 0 Not
change
0 1 Decrease
1 0 Increase
1 1 Not
change
20,21: FWD/REV jog 1 command input (JOGF1 / JOGR1).
26: Acc/Dec time terminal function.
•
Priority of acc/dec time: acc/dec time defined by No. 26 of terminal acc/dec time defined by F03.09 and
F03.10.
Acc/Dec time terminal 1 (No. 26)
Acc/Dec selection
0 Acc/dec
time1
1 Acc/dec
time
2
123
41,42: Coast to stop NO/NC input.
•
After inverter receives command, it stops output at once, the load will coast to stop according to
mechanical inertia.
43: Emergency stop.
•
After inverter receives command, it decelerates to stop. The dec time is set by F03.17.
44,45: NO/NC input for external fault.
•
Inverter shows external device’s fault after receiving fault signal and coast to stop.
•
Two input modes for fault signal: NO or NC.