Shenzhen Hpmont Technology Co., Ltd.
Chapter 8 Parameter
HD09 Series User Manual V1.1
-
29
-
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
F06.01
Multi-step frequency
Command 2
F00.09 - F00.08
5.0Hz
0.1Hz
○
F06.02
Multi-step frequency
Command 3
F00.09 - F00.08
5.0Hz
0.1Hz
○
F06.03
Multi-step frequency
Command 4
F00.09 - F00.08
5.0Hz
0.1Hz
○
F06.04
Multi-step frequency
Command 5
F00.09 - F00.08
5.0Hz
0.1Hz
○
F06.05
Multi-step frequency
Command 6
F00.09 - F00.08
5.0Hz
0.1Hz
○
F06.06
Multi-step frequency
Command 7
F00.09 - F00.08
5.0Hz
0.1Hz
○
F08: Motor Parameters
F08.00
Rated power of motor
0.2 - 5.5kW
Depende
nt on
HD09
0.1kW
×
F08.01
Rated voltage of motor
0V - inverter’s rated voltage
1V
×
F08.02
Rated current of motor
0.01 - 99.99A
0.01A
×
F08.03
Rated frequency of motor
1 - 1000Hz
50Hz
1Hz
×
F08.04
Rated Rpm of motor
1 - 24000rpm
Depende
nt on
HD09
1rpm
×
F08.06
Parameter auto-tuning of
motor
0: Auto-tuning is disabled
1: Stationary auto-tuning
0 1
×
F08.07
Stator resistance of motor
0.00 - 99.99Ω
Depende
nt on
HD09
0.01Ω
×
F09: V/f Control Parameters
F09.01
V/f frequency value F3
F09.03 - 100.0% (F08.03)
100.0%
0.1%
×
F09.02
V/f voltage value V3
F09.04 - 100.0% (F08.01)
100.0%
0.1%
×
F09.03
V/f frequency value F2
F09.05 - F09.01 (F08.03)
0.0%
0.1%
×
F09.04
V/f voltage value V2
F09.06 - F09.02 (F08.01)
0.0%
0.1%
×
F09.05
V/f frequency value F1
0.0% - F09.03 (F08.03)
0.0%
0.1%
×
F09.06
V/f voltage value V1
0.0% - F09.04 (F08.01)
0.0%
0.1%
×
F09.07
Torque boost
0.0 - 30.0%
2.0%
0.1%
×
F09.08
Cut-off point used for
manual torque boost
0.0 - 50.0% (F08.03)
30.0%
0.1%
○
F09.09
Motor transfer
compensation gain
0.0 - 300.0%
0.0%
0.1%
○