Chapter 8 Parameter
Shenzhen Hpmont Technology Co., Ltd.
-
28
-
HD09 Series User Manual V1.1
Ref. Code
Function
Setting Range
Default
Unit
Attribute Setting
F04.02
Feedback source selection
0: AI analogue feedback
1: Terminal pulse feedback
0 1
×
F04.03
Setting digital reference
0.0 - 100.0%
0.0%
0.1%
○
F04.04
Proportional gain (P)
0.00 - 10.00
2.00
0.01
○
F04.05
Integral time (I)
0.01 - 10.00s
1.00s
0.01s
○
F04.07
Differential time (D)
0.00 - 10.00s
0.00s
0.01s
○
F04.08
Differential amplitude limit
value
0.0 - F00.08
20.0Hz
0.1Hz
○
F04.09
Sampling cycle (T)
0.01 - 50.00s
0.10s
0.01s
○
F04.10
Bias limit
0.0 - 20.0%
2.0%
0.1%
○
F04.16
Integral regulation
selection
0: Stop integral regulation when the
frequency reaches the upper or lower
limit
1: Continue the integral regulation
when the frequency reaches the upper
or lower limit
0 1
×
F04.17
PID output filter time
0.01 - 10.00s
0.05s
0.01s
○
F04.18
PID output reverse
selection
0: PID regulation disable reverse
(When PID output is negative, 0 is the
limit)
1: PID regulation enable reverse
0 1
×
F04.19
PID output reverse
frequency’s upper limit
0.0 - F00.08
50.0Hz
0.1Hz
×
F05: External Reference Curve Parameters
F05.01
Minimum reference of line
0.0% - F05.03
0.0%
0.1%
○
F05.02
Minimum reference
corresponding value of
line
0.0 - 100.0%
0.0%
0.1%
○
F05.03
Maximum reference of line
F05.01 - 100.0%
100.0%
0.1%
○
F05.04
Maximum reference
corresponding value of
line
0.0 - 100.0%
100.0%
0.1%
○
F05.17
Skip frequency
F00.09 - F00.08
0.0Hz
0.1Hz
×
F05.20
Range of skip frequency
0.0 - 30.0Hz
0.0Hz
0.1Hz
×
F06: Multi-step Speed Parameters
F06.00
Multi-step frequency
Command 1
F00.09 - F00.08
5.0Hz
0.1Hz
○