background image

1. 

Thought should be given to exactly what you would  

like the Light Patrol to do. This may influence your  
decision as to where to place it. If for instance you  
simply wish the lights to turn on when someone  
approaches your front door, the sensor should  
monitor the pathway leading to the front door. If  
however, you have a particular problem area where  
intruders can enter silently and undetected, you need  
the Light Patrol to monitor this area.
Added security can be achieved by linking the unit  
to both outdoor lights and lights or buzzer inside  
the house.
The Light Patrol monitors a 180

°

field of view. In  

practice, however, that scanning width may be toowide.  
If for instance, 

the neighbour’s 

driveway is creating  

nuisance switching (your unit is triggered by cars and  
people next door) the field of view may need to be  
restricted.
Four plastic blinkers are supplied. These can be  
inserted into the corner/s of the lens and will blind  
the sensor by approx. 13

°

for each blinker used. All  

four blinkers will reduce field of view to approx. 130

°

.  

These may be inserted one side or the other or shared

depending on the problem that you are attempting  to  

overcome. (see figure 1)
2. Before installation make sure that the power is off

on that particular circuit. Remove the fuse or turn off  
the circuit breaker at the switchboard.
3. Choose a mounting position approximately 2 metres
above the area that you wish to monitor. (The unit may
be mounted to a height of 4 metres.)
4. Remove the base cover and screw it to the wall or  
eave through the two screw holes. If brick or concrete,  
wall plugs may be needed. Note:

‘Bottom’ 

is downward.  

Or, in the case of eave mounting, 

‘bottom’ 

is closest to  

the wall (facing away from monitoring area).
5. Connect the Light Patrol to the power source  
according to the 

‘wiring 

instructions'. Then screw the  

main unit to the base cover.
6. Turn the power on. Start 

‘walk test’

(see TEST  

MODE on page 3).
Note: Up and down direction of the Light Patrol is  
called the 

‘tilting angle’. 

The bigger the tilting angle  

the shorter the detection distance 

the most ideal tilt  

angle is between 0

°

and 10

°

(see figure 2.)

Variable field of view

Avoid straight-on monitoring as a person  
may not be detected walking straight  

‘into’ the sensing

area.

Better to mount obliquely to the expected  
direction of approach so that the person  
walks 

‘through’ 

the sensing area.

6

Installation

Figure 2

.

Figure 1

.

Содержание 630/3

Страница 1: ...efore installing 3 Make sure the power wiring comes from a circuit protected by a suitable fuse or circuit breaker 4 For outdoor installation a location under eaves is preferable 5 This unit must be installed by a licensed electrician according to local codes and regulations 3 Features 4 Wheninstallingthesecuritysensorpay specialattentiontothesepoints Directed at swimming pools and ponds The movem...

Страница 2: ... shared depending on the problem that you are attempting to overcome see figure 1 2 Before installation make sure that the power is off on that particular circuit Remove the fuse or turn off the circuit breaker at the switchboard 3 Choose a mounting position approximately 2 metres above the area that you wish to monitor The unit may be mounted to a height of 4 metres 4 Remove the base cover and sc...

Страница 3: ... within 1 2 seconds The light s will now remain on until manually switched off To return the Light Patrol to the Auto Mode turn the power off for longer than 10 seconds and then switch back on Cat 630 3A and 630 3ABL requires special wiring for manual override see figure 5 Cat 630 3A and 630 3ABL Wiring to terminal block Cat 630 3A and 630 3ABL with by pass switch Protected position Under eave if ...

Страница 4: ... 1 Power not available Check connections switches and fuse 2 Faulty globe Replace globe 3 Incorrect wiring Recheck all wiring 4 Controls incorrectly set Change detection angle Change light adjustment 5 Sensor positioned in wrong direction Change position and direction of sensor Light switches on for no apparent reason 1 Air conditioner heater vents in proximity of sensor Reposition and redirect se...

Отзывы: