Item
Specification
Maximum operating noise level (with IT rack doors
open)
101 dBa
Power cords
IEC 60309 32/30A 220/415V 6h/IP44 (Quantity 2)
Maximum branch circuit size: 32A
NEMA L22-20P 277/480V 4P/5W (Quantity 2)
Maximum branch circuit size: 20A
Thermal and air flow performance
Thermal and air flow performance
parameters
Single rack
Air temperature—Inlet to rack-mounted
components
User adjustable up to 40ºC (104ºF)
Chilled water temperature
7º-32°C (45º-89.6°F)
Total rack-mounted component air flow
With 4 fans: up to 10,000 CFM (16,990 m3/h)
With 3 or 4 fans: 7,500 CFM (12,743 m3/h)
Operating 150 kW maximum
Performance is dependent on water temperature and air
temperature set point.
Chilled water flow rate
270 l/min (71.3 US gal/min)
Chilled water pressure differential at flow
necessary to meet thermal specifications
15 psid
Server heat load
150 kW maximum
For more information, see "Determining heat load capacities"
in the
HPE Adaptive Rack Cooling System Site Preparation
Guide
.
Environmental specifications
Parameter
Value
Room temperature:
Recommended minimum/maximum
10°C (50°F)/50°C (122°F)
Humidity:
Recommended range
8% to 90% relative humidity, non-condensing
Air quality
Standard Hewlett Packard Enterprise
requirements
68
Specifications