●
Place the workstation in an area with adequate ventilation. Provide at least 6 inches of clearance
at the front and back of the workstation as shown in the following figure.
Your workstation might look different than the one shown.
Figure 1-5
Proper workstation ventilation
●
Ensure that the ambient air temperature surrounding the workstation falls within the published limit.
NOTE:
The ambient upper limit of 35°C is only good up to 5000 feet elevation. There is a 1°C
per 1000 feet derating above 5000 feet. So at 10,000 feet the upper ambient air temperature limit
is 30°C.
●
For cabinet installation, ensure adequate cabinet ventilation and ensure that the ambient
temperature within the cabinet does not exceed published limits.
●
Never restrict the incoming or outgoing airflow of the workstation by blocking any vents or air intakes
as shown in the following figure.
Figure 1-6
Proper workstation placement
Features
This section describes several features that improve workstation performance and usability. It presents
these topics:
ENWW
Features
13
Содержание Workstation Z600
Страница 1: ...HP 600 Workstation Maintenance and Service Guide ...
Страница 4: ...iv About this guide ENWW ...