UPS operations 42
For information on what to do if the self-test detects a problem, see "Troubleshooting (on page
52
)."
Silencing an audible alarm
To silence an alarm, press the Test/Alarm Reset button ("
UPS front panel controls
" on page
8
).
IMPORTANT:
•
Although the audible alarm silences, the condition that caused the alarm to sound may still
exist.
•
If a utility power failure caused the alarm, the alarm silences after power is restored.
For information about audible alarm conditions, see "LED and audible alarm troubleshooting ("
LED
troubleshooting
" on page
52
)."
Verifying the REPO port connection
NOTE:
While testing, operate connected equipment in a safe test mode so the effects do not
disrupt critical operations.
After connecting the REPO port (on page
21
):
1.
Initiate a REPO by closing the REPO contact.
The Self Test, Battery Fault, Site Wiring Fault, Overtemperature, Overload, and Utility LEDs flash.
CAUTION:
If the polarity is reversed while connecting the REPO port, the UPS powers up
normally.
2.
Verify proper connection of the REPO port:
a.
Power up the UPS ("
Starting power to the load
" on page
26
).
b.
Disconnect the REPO port.
c.
Reconnect the REPO port.
If the polarity is correct, the REPO connectors can be disconnected, and then reconnected,
without initiating a REPO.
d.
Verify that the UPS remains in Operate mode (on page
38
).
e.
If a REPO is initiated, the polarity is reversed. Check and correct the connections.
Powering down the UPS
1.
Shut down all load devices.
2.
Press the Off button to take the UPS out of Operate mode. Power to the load receptacles ceases.
The On Battery LED and Load Level indicator flash.
3.
Disconnect the UPS from utility power.
4.
Wait at least 60 seconds for the UPS internal circuitry to discharge.
Содержание Presario R3000 - Notebook PC
Страница 1: ...HP UPS R T3000 User Guide Part Number 507932 002 December 2009 Second Edition ...
Страница 6: ...Grounding methods to prevent electrostatic discharge 74 Acronyms and abbreviations 75 Index 77 ...
Страница 21: ...Installation 21 Connecting the USB communications port Connecting the REPO port ...
Страница 29: ...Installation 29 Installing the extension bars if included ...
Страница 31: ...Installation 31 4 Attach the chassis to the rack using the supplied screws Connecting the battery leads ...
Страница 32: ...Installation 32 Attaching the ERM front bezel ...
Страница 76: ...Acronyms and abbreviations 76 UPS uninterruptible power system USB universal serial bus ...