Troubleshooting 54
•
Overload
The load is supported, but not protected while in Auto-Bypass mode.
Action
:
1.
If power management software is being used, check the log files to obtain specific error information
to help identify the problem.
For more information about the causes of a general fault condition, see the HP Power Manager user
guide available for download from the HP website (
http://www.hp.com/go/rackandpower
).
2.
Verify that no blockage of airflow to the front bezel and rear panel exists.
UPS is in Converter Off mode
Fault conditions cause the UPS to transfer to Converter Off mode from Standby mode (on page
38
) only.
If the UPS is powering the load, fault conditions cause the UPS to transfer to Auto-Bypass mode instead.
If a fault condition exist and the UPS is running in Auto-Bypass mode (on page
39
), press the Off button to
transfer the UPS to Converter Off mode.
The load is not supported while in Converter Off mode.
The following fault conditions trigger Converter Off mode:
•
Inverter AC over voltage
•
Inverter AC under voltage
•
Rectifier input over current
•
Inverter output over current
•
Inverter fault
•
Heat sink over temperature
Action:
1.
If power management software is being used, check the log files to obtain specific error information
to help identify the problem.
For more information about the causes of a general fault condition, see the HP Power Manager user
guide available for download from the HP website (
http://www.hp.com/go/rackandpower
).
2.
Verify that no blockage of airflow to the front bezel and rear panel exists.
General alarm condition
Action
:
1.
If power management software is being used, check the log files to obtain specific error information
to help identify the problem.
For more information about the causes of a general alarm condition, see the HP Power Manager
user guide available for download from the HP website (
http://www.hp.com/go/rackandpower
).
2.
Check the batteries:
a.
Allow the UPS batteries to charge for 24 hours.
Содержание Presario R3000 - Notebook PC
Страница 1: ...HP UPS R T3000 User Guide Part Number 507932 002 December 2009 Second Edition ...
Страница 6: ...Grounding methods to prevent electrostatic discharge 74 Acronyms and abbreviations 75 Index 77 ...
Страница 21: ...Installation 21 Connecting the USB communications port Connecting the REPO port ...
Страница 29: ...Installation 29 Installing the extension bars if included ...
Страница 31: ...Installation 31 4 Attach the chassis to the rack using the supplied screws Connecting the battery leads ...
Страница 32: ...Installation 32 Attaching the ERM front bezel ...
Страница 76: ...Acronyms and abbreviations 76 UPS uninterruptible power system USB universal serial bus ...