Troubleshooting 57
Overload condition
All the load LEDs are illuminated.
Action
:
1.
Power down the UPS ("
Powering down the UPS
" on page
42
).
2.
Remove one or more load devices to reduce the power requirements.
3.
Wait at least 5 seconds and restart the UPS.
4.
If the condition persists, verify that the load devices are not defective.
Checksum failure error
A Checksum failure error occurs when executing a bad load sequence, or having an incorrect EEPROM
map while loading software through the serial or USB port.
Action:
1.
Rerun the firmware upgrade.
2.
If the condition persists, contact an HP authorized service representative.
UPS does not start
Action
:
1.
Be sure that the power cord is plugged in to a utility power receptacle.
2.
Check the power source at the utility power receptacle.
Low battery shutdowns
Ungraceful shutdown of attached servers occurs when the UPS is in a low battery condition.
Action
:
1.
Verify that the power management software is not delaying the shutdown of attached servers when
the UPS is in a low battery condition.
2.
Allow the UPS batteries to charge for 24 hours.
3.
If the Battery Fault LED is red, replace the batteries ("
UPS battery replacement procedure
" on page
46
).
UPS does not provide the expected backup time
Action:
1.
If the Overload LED ("
UPS front panel controls
" on page
8
) is illuminated, remove one or more load
devices to reduce the power requirements.
2.
Power down the UPS ("
Powering down the UPS
" on page
42
).
3.
Allow the UPS batteries to charge for 24 hours.
4.
Initiate a self-test ("
Initiating a self-test
" on page
41
).
Содержание Presario R3000 - Notebook PC
Страница 1: ...HP UPS R T3000 User Guide Part Number 507932 002 December 2009 Second Edition ...
Страница 6: ...Grounding methods to prevent electrostatic discharge 74 Acronyms and abbreviations 75 Index 77 ...
Страница 21: ...Installation 21 Connecting the USB communications port Connecting the REPO port ...
Страница 29: ...Installation 29 Installing the extension bars if included ...
Страница 31: ...Installation 31 4 Attach the chassis to the rack using the supplied screws Connecting the battery leads ...
Страница 32: ...Installation 32 Attaching the ERM front bezel ...
Страница 76: ...Acronyms and abbreviations 76 UPS uninterruptible power system USB universal serial bus ...