Specifications
E-10
HP ProLiant BL p-Class System Setup and Installation Guide
HP CONFIDENTIAL
Writer: Christine Portillo File Name: j-appe Specifications.doc
Codename: ICE Part Number: 230852-002 Last Saved On: 11/20/02 5:01 PM
Table E-5: Operating and Performance Specifications for Power Distribution
Devices
continued
Power Bus Box
Mini Bus Bar
Scalable Bus Bar
Total max input
current at min voltage
69.44 A at
-43.2 VDC
208.32 A at
-43.2 VDC
347.2 A at
-43.2 VDC
(equivalent of 175 A
per feed)*
Total max input
current at nominal
voltage
62.5 A at -48 VDC
187.5 A at -48 VDC
312.5 A at -48 VDC
(equivalent of
156.25 A per feed)*
Max current per
power feed*
70 A
210 A
210 A
Max local ambient
temperature
65°C (149°F)
65°C (149°F)
65°C (149°F)
* All systems support redundant power configurations by using separate power inputs for each bus.
Scalable bus bars provide dual power inputs (P1 and P2) for each bus.