Troubleshooting 90
Test
LED flash error code
Description
1
Permanently on
DRAM failure
2
2 flashes
DMA Mem to Mem error
3
3 flashes
IRQ error
4
4 flashes
Ethernet error
5
5 flashes
Serial loop back error
6
6 flashes
RTC error
Event notification messages do not appear on
console screen
Action:
If you are using SLES 9, upgrade the KDE or use a different desktop, such as GNOME.
Event notifications are not being sent
Action:
While email and SNMP trap notifications must be set up on their respective screens, notifications
must also be enabled per event on the Event Notifications screen ("
Event Notifications menu
" on page
64
).
FTP error messages appear when connecting
through Linux
Symptom:
When connecting to FTP through Linux, error messages about bad commands appear.
Action:
The user can log in although the error messages appear.
Flash update fails over a serial connection
Action:
Disable any serial port being configured during the flash update, such as iLO, or use an FTP
connection.
HP SIM lists a discovered UPS as Unmanaged in the
System Type column
Action:
1.
Delete the discovered UPS from HP SIM.
2.
Using the management module web interface, add the HP SIM server as a Manager on the SNMP
Managers tab (on page
62
).
3.
Rediscover the UPS in HP SIM.