11
1. Insert the red test lead into the
V A
terminal, blue test lead into the
V B
terminal, yellow test lead to
V C
input terminal and black test lead to the
COM
input terminal.
2. Connect the red test leads (
VA
input terminal), blue test leads (
VB
input
terminal) and yellow test leads (
VC
input terminal) to the corresponding
three phases loaded live wire. Black test lead (COM input terminal) to the
corresponding three phases loaded neutral wire.
3. Press
SELECT
to select phase location, the display shows the
corresponding phase symbol.
VA
means the first phase
A
,
VB
means
the first phase
B
,
VC
means the first phase
C
.
4. The display shows the corresponding True RMS voltage value and
frequency value of each phase.
5. Press
MAX
/▲
, the LCD displays MAX, it starts recording the maximum
AC voltage True RMS value. Press
MAX
/▲
again to show the current AC
voltage True RMS value.
6. Press
MIN
/▼
the LCD displays MAX, it starts recording the minimum AC
voltage True RMS value. Press
MAX
/▼
again to show the current AC
voltage True RMS value.
7. The display shows
9999
when the input voltage is higher than 600V rms.
Note
●
When the measurement has been completed, disconnect the connection
between the testing leads and the circuit under test and remove testing
leads from the input terminals.
B. AC Current (main display) + AC Voltage (secondary display)
Measurement
The AC current ranges are: 40A, 100A, 400A and 1000A
The AC Voltage ranges are: 15V, 100V, 300V and 600V
To measure AC c AC voltage, connect the Meter as follows:
1. Press the
Kw
to select AC Current (main display) + AC Voltage
(secondary display) range.
2. Press the lever to open the transformer jaw.
3. Center the conductor within the transformer jaw, then release the Meter
slowly until the transformer jaw is completely closed, Make sure the
conductor to be tested is placed at the center of the transformer jaw,