B-16
Table B-22.
A2994A PowerTrust UPS Specifications
.
Description
Specification
Electrical Specifications:
AC Line Input:
Rated Voltage
100-120/200-240 VAC 50/60 Hz (Auto-ranging)
Rated Current
14 to 12 Amps and 7 to 6 Amps
(20 Amp max branch circuit overcurrent protection)
AC Output:
Output VAC
(On Line Power)
Approximately equal to AC line input power
Output VAC
(On Battery)
115 VAC or 230 VAC at 50/60Hz
(+ 10% with full load)
Range VA/Watts
1300/1300 @ 0.5 to 1.0 power factor
Transfer Time
AC Failure - < 10 msec to switch to battery power
AC Restored -5 Second delay returning to input AC phase lock
Phasing
Phase locked to within 5º of input utility AC
Safety Agency Approvals
Agency approvals: UL, CSA, and TUV
Battery:
Type
Maintenance-free, sealed, computer grade, lead-acid type
Nominal open
circuit voltage
60 VDC
Reserve time
Approximately 15 minutes (at full load)
Battery Recharge
Time
< 14 Hours with output switch in the ON position
(after full discharge)
< 24 Hours with output switch in the OFF position
(after full load discharge)
Optimum Battery
Lifetime
3.5 to 5 years