B-12
i.
Derate maximum operating temperature -1.98° F per 1,000 feet over 7,500 feet
(-1.1° C per 305 meters above 2,286 meters)
Table B-19.
Expansion Cabinets -
Environmental Specifications.
Description
Specification
Temperature Requirements:
Recommended operating temperature
20° to 25° C (68.0° to 77.0° F)
Operating temperature range
5° to 40° C (41° to 104° F)
Maximum Operating Rate of Change
20° C (36° F) per hour
Non-Operating (Storage) Temperature Range -40° to 70° C (- 40° to 158° F)
Humidity Requirements:
Recommended Operating Humidity
40% to 60% Relative Humidity
Operating Humidity
15% to 80% Relative Humidity at 40° C (104° F)
Non-Operating (storage) Humidity
90% Relative Humidity at 65° C (149° F)
Heat Dissipation:
360 Watts (Maximum) (1227 BTU/hour)
Altitude Requirements:
Maximum Operating
3,000.0 meters (9842.5 feet)
i
Maximum non-operating
4,572 meters (>15,000 feet)
Vibration Requirements:
Operating Random (5-500Hz)
Approx 0.21 G rms
Sinusoidal Sweep Survival (5-500Hz)
0.5 g (0 peak)
Random survival (5-500Hz)
Approx 2.09 G rms
Shock Requirements:
End Use Handling
10.20 cm (4.0 inch) Free-fall Drop
Transportation
30
g
trapezoidal
(Delta velocity of 368.0 cm/sec)
Acoustic Requirements:
Sound Power
4.2 Bels (A-Weighted)
Bystander sound pressure (L
p
A)
42 dB (A-Weighted)
Содержание 3000/9x9KS Series
Страница 10: ...x ...
Страница 38: ...A 4 Figure A 1 Space Planning Grid Sheet ...
Страница 39: ...A 5 Figure A 2 System Cutouts ...
Страница 70: ...B 28 ...
Страница 75: ...C 5 Figure C 3 Space Planning Grid ...
Страница 76: ...C 6 Figure C 4 K Class Equipment Profiles ...
Страница 77: ...C 7 Figure C 5 T Class Equipment Profiles ...
Страница 82: ...C 12 ...