B-14
Table B-21.
A2941A PowerTrust UPS Specifications
.
Description
Specification
Electrical Specifications:
AC Line Input:
Rated Voltage
100-120/200-240 VAC 50/60 Hz (Auto-ranging)
(Compatible with 127 VAC input power systems)
Rated Current
6.75/3.80 Amps
AC Output:
Output VAC
(On Line Power)
Same as AC line input power
Output VAC
(On Battery)
115 VAC or 230 VAC at 50/60Hz
(+ 10% with full load)
Range VA/Watts
650/420 @ 0.65 power factor
760/420 @ 0.55 power factor
Transfer Time
AC Failure - < 10 msec to switch to battery power
AC Restored -5 Second delay returning to input AC phase lock
Phasing
Phase locked to within 5º of input utility AC
Safety Agency Approvals
UL, CSA, TUV, FI, and CB Certificate
Fuse
Cartridge Type - 10 Amp 250VAC
Battery:
Type
Maintenance-free, sealed, lead-acid type
Nominal open
circuit voltage
24 VDC
Reserve time
Approximately 15 minutes (at full load)
Battery Recharge
Time
14 Hours
Optimum Battery
Lifetime
3.5 to 5 years