![Hoval TopTronic RS-10 Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/hoval/toptronic-rs-10/toptronic-rs-10_user-instructions_2170801026.webp)
26
Advanced Parameter Table
430293ENG-Dec01
Factory settings
No.
Parameter Function
Adj. Range
133B 1B
2B
23B
233B 2233B
223B
3
203B
Current Setting
Pump seizure protection
0,1
1
1
1
1
1
1
1
1
1
0: Off
X
X
X
X
X
X
X
X
X
69
1: On
X
X
X
X
X
X
X
X
X
C/return protect during Blr turnon
0,1
1
1
1
1
1
1
0: Off
X
X
X
X
X
X
70
1: On
X
X
X
X
X
X
71 Extended burner operation time
0...20 min
10 min
10 min
10 min
10 min 10 min
20 min
72 1st stage differential
2...30K
6 K
6 K
6 K
6 K
6 K
10 K
73 2nd stage differential
2...30K
12 K
12 K
74 2nd stage delay
0...60min
10 min 10 min
10 min
75 Lock 2stage with Outdoor temp
Aus, -15°C...30°C
10°C
10°C
10°C
Hot water power select for 2stage
1...3
3
3
3
1: With outdoor temp and delay
X
X
X
2: With outdoor temp without delay
X
X
X
76
3: Without limitations
X
X
X
Control input programming X1-33
0,1,2
0
0
2
2
2
0: Dom water heat (auto/Blr/Elec)
X
X
X
X
1: Priority inversion
X
X
X
80
2: Burner operation
X
X
X
X
X
Alarm logic signals
0,1
1
1
1
1
1
1
1
1
1
0: Off
X
X
X
X
X
X
X
X
X
81
1: On
X
X
X
X
X
X
X
X
X
82
RESET
RESET
X
X
X X X X X
X X
83 Relay Test
alle Relais / all relays
X
X
X X X X X
X X
X = Possible settings