Advanced Parameter Table
430293ENG-Dec01
Factory settings
No.
Parameter Function
Adj. Range
133B
1B
2B
23B
233B 2233B
223B
3
203B
Current Setting
1 Frost
Protection
-20°C...10°C
0
0
0
0
0
0
0
0
0
2 Summer switch-off
Aus, 10°C...30°C
17°C 17°C
17°C
17°C
17°C
17°C
17°C 17°C
17°C
3 Minimum outdoor temperature
-20...0
-10
-10
-10
-10
-10
-10
-10
-10
-10
4 Maximum flue gas temperature
70°C...250°C
250°C
250°C 250°C 250°C 250°C 250°C
250°C
5 Maximum boiler temperature
10°C...95°C (90°C Gas)
80°C 80°C
85°C 85°C 85°C 85°C 85°C
85°C
6 Boiler return temperature
0...70°C
0
38°C
38°C
38°C
38°C
38°C
7 Blr circ Temp rise (Above mix circ) 0(-5K 133B,3)...20K) 0K
8 K
8 K
12 K
12 K
8K
8 K
8 Pump overrun
0...15 min
5 min 5 min 5 min 5 min 5 min 5 min 5 min 5 min
5 min
9 Boiler minimum temperature
10°C(0°C 203B)...95°C
48°C
48°C
48°C
48°C
48°C
0 °C
Type of hot water priority
1,2,3
3
2
2
3
3
3
3
3
1: None
X
X
X
X
X
X
X
X
2: Priority
X
X
X
X
X
X
X
X
10
3: Priority with reservation
X
X
X
X
X
X
11 Maximum hot water temperature
40°C...80°C
60°C 60°C
60°C
60°C
60°C
60°C
60°C
60°C
Type of calorifier sensor
1,2
2
2
2
2
2
2
2
2
1: Thermostat
X
X
X
X
X
X
X
X
12
2: Sensor
X
X
X
X
X
X
X
X
13 Protection against Legionella
0...8
8
8
0
0
0
0
0
0
14 Night water load
0.1...1.0
0.3
0.3
15 Dom H/water installation load temp 0...50K
20 K
20 K
25 K
25 K
25 K
25 K
25 K
25 K
20 Influence room temp on blr circ KK 0...2.5
0.5
0.5
1.0
1.0
1.0
1.0
1.0
1.0
Blr circ automatic adaption KK
0,1
0
1
1
0
0
0
0
0
0: Off
X
X
X
X
X
X
X
X
21
1: On
X
X
X
X
X
X
X
X
Boiler circuit user index KK
1,2,3
2
2
2
2
2
2
2
2
1: 1.00
X
X
X
X
X
X
X
X
2: 1.31
X
X
X
X
X
X
X
X
22
3: 2.00
X
X
X
X
X
X
X
X
23 Blr circ derivative action time KK
0...6h
2h
2h
1h
1h
1h
1h
1h
1h
Blr circ ext sensor detection KK
0,1,2
0
0
0
0
0
0
0
0
0: Average value
X
X
X
X
X
X
X
X
1: External sensor 1
X
X
X
X
X
X
X
X
24
2: External sensor 2
X
X
X
X
X
X
X
X
27 Boiler circ constant temp reg KK
0..95 (90°C Gas) °C
0
0
0
0
0
0
30 Influence room temp blr circ MK1
0...2.5
0.5
1.0
1.0
1.0
1.0
1.0
1.0
Mixed circ 1 auto adaption MK1
0,1
1
1
1
1
1
1
1
0: Off
X
X
X
X
X
X
X
31
1: On
X
X
X
X
X
X
X
32 Mixed circuit minimum temp MK1
0...95°C (90°C Gas)
0
0
0
0
0
0
0
33 Mixed circuit maximum temp MK1
10°C...95°C (90°C Gas)
80°C
80°C
80°C
80°C
80°C 80°C
80°C
Mixed circuit 1 user index MK1
1,2,3
2
2
2
2
2
2
2
1: 1.00
X
X
X
X
X
X
X
2: 1.31
X
X
X
X
X
X
X
34
3: 2.00
X
X
X
X
X
X
X
35 Mix circ1 derivative action time MK1 0...6h
2h
1h
1h
1h
1h
1h
1h
Mix circ 1 ext sens. detection MK1 0,1,2
0
0
0
0
0
0
0
0: Average value
X
X
X
X
X
X
X
1: External sensor 1
X
X
X
X
X
X
X
36
2: External sensor 2
X
X
X
X
X
X
X
40 Influence room temp mix circ 2MK2 0...2.5
0.5
1.0
1.0
X = Possible settings