OvERvIEW Of SETTIngS
RETURN CONTR
Par.
Designation
Factory
10
20
30
40
50
Lev.
1
Minimum limit return temperature / reference value return
temperature
38 °C
HF
2
Switch-off difference
2 k
HF
3
Pump follow-on time
1 min
HF
SOlAR
Par.
Designation
Factory
10
20
30
40
50
Lev.
1
Switch-on difference
10 k
HF
2
Switch-off difference
5 k
HF
3
Minimum running time SOP
3 min
HF
4
Solar collector maximum temperature
100 °C
HF
5
Solar tank maximum limit (KSPF)
65 °C
HF
6
Solar mode of operation
2
HF
7
Heat generator cycle lock (only when parameter 06=1,3,4)
0,5 h
HF
8
Solar priority parallel changeover
10 k
HF
9
Solar heat balance
OFF
HF
SOLAR
RESET
Reset heat balance
HF
11
Volumetric fl ow rate
0,0 l/ min
HF
0,0 l/ IMP
12
Density, medium
1,05 kg/ l
HF
13
Specifi c thermal capacity, medium
3,6 kJ/ kgk
HF
14
Final switching-off temperature
120 °C
HF
15
Test cycle solar charging switch-over
10 min
HF
16
Switch-over temperature (SLVF)
60 °C
HF
17
Solar minimum temperature
OFF
HF
SOlID FUEl
Par.
Designation
Factory
10
20
30
40
50
Lev.
1
Minimum temperature
60 °C
HF
2
Maximum temperature
95 °C
HF
3
Switch-on difference
10 k
HF
4
Switch-off difference
5 k
HF
5
Clock block, heat generator
15
HF