43
4 211 326 / 01
OvERvIEW Of SETTIngS
MIX. VAlVE-2
Par.
Designation
Factory
10
20
30
40
50
Lev.
1
Type of reduced operation
ECO/ ABS
HF
2
Heating system (exponent)
Mk= 1,10
HF
3
Room override (in connection with room sensor)
3
HF
4
Room factor
100 %
HF
5
Adaptation heating curve
ON
HF
6
Switch-on optimisation
1
HF
7
Heating limit
0,5
OEM
8
Room frost protection limit
10 °C
HF
9
Room thermostat function
OFF
HF
10
Outside temperature allocation
0
HF
11
Constant temperature reference value
20 °C
HF
12
Minimum temperature limit
10 °C
HF
13
Maximum temperature limit
55/ 75 °C
HF
14
Temperature elevation/ abatement heating circuit
0/ 8 k
HF
15
Pump follow-on
5 min
HF
16
Screed function
OFF
HF
18
P-portion Xp
2,0 %/ k
OEM
19
Scanning time Ta
20 s
OEM
20
I-portion Tn
270 s
OEM
21
Running time servomotor
150 s
HF
22
End position function, valve
1
OEM
23
Room control K-factor
8
HF
24
Room control Tn-factor
35 min
HF
25
Vacation mode
STBY
HF
36
Minimum value override
OFF
HF
37
Mixer lead time
OFF
HF
38
Regulation offset
0
HF
50
Cooling switch-on point, OT
OFF
HF
51
Cooling max. point, OT
35 °C
HF
52
Cooling reference fl ow temp. at switch-on point
18 °C
HF
53
Cooling reference fl ow temp. at max. point
24 °C
HF
54
Cooling reference room temp. at switch-on point
23 °C
HF
55
Cooling reference room temp. at max. point
28 °C
HF
56
Min. temp. cooling
18 °C
OEM
Name heating circuit (max. 5 letters)
XXXXX
HF