14
Operations
Installation Instructions
Venting
CAUTION - RISK OF ASPHYXIATION: Do not run
machine indoors or in an enclosed area without the
required venting, as exhaust fumes may be
hazardous to your health.
CAUTION: All venting must be in accordance with
applicable federal and state laws, and local ordi-
nances. Consult local heating contractors.
IMPORTANT: A draft regulator shall be installed.
INSTALLER UNE HOTTE DE TIRAGE.
If the pressure washer is to be used in an enclosed
area, a flue must be installed to vent burner exhaust to
the outside atmosphere. Exhaust gases should not be
vented into a wall, a ceiling, or a concealed space of a
building. Be sure the flue is the same size as the burner
exhaust vent on the pressure washer. Poor draft will
cause the pressure washer to soot and not operate
properly. When selecting the location for installation,
beware of poorly ventilated locations or areas where
exhaust fans may cause an insufficient supply of
oxygen available for the amount of fuel being burned. If
it is necessary to install the machine in a poorly venti-
lated area, outside fresh air may have to be piped to the
burner and a fan installed to bring sufficient air into the
machine. Locate the pressure washer so that the flue
will be as straight as possible and protrude through the
roof at a proper height and location to provide adequate
draft. This oil fired pressure washer must have a draft
regulator installed in the flue (available from most
heating contractors). A draft regulator will permit proper
upward flow of exhaust flue gases.
Electrode Setting:
Periodically Check Wiring Connections. If
Necessary To Adjust Electrodes, Use Diagram.
Burner Air Adjustment
The oil burner on this machine is preset for operation at
altitudes below 500 feet. If operated at higher altitudes,
it may be necessary to adjust the air band for a #1 or #2
smoke spot on the Bacharach scale.
To adjust, start machine and turn burner ON. Loosen
two locking screws found on the air band and close air
band until black smoke appears from burner exhaust
vent. Note air band position. Next, slowly open the air
band until white smoke just starts to appear. Turn air
band halfway back to the previously noted position.
Tighten locking screws.
For higher altitudes, the air band opening may need to
be increased; for lower altitude, the air band may need
to be decreased.
For higher humidity, the air band opening may need to
be increased; for lower relative humidity, the air band
may need to be decreased.
For higher ambient temperatures the air band opening
may need to be increased; for lower ambient tempera-
tures, the air band opening may need to be decreased.
Adjust to your operating location's environment as-
needed for best smoke spot and performance
compliant with local, state, and federal regulations.
CAUTION: If white smoke appears from burner
exhaust vent during start-up or operation, discon-
tinue use and readjust air bands.
NOTE: If a flue is installed, have a professional
serviceman adjust your burner for a #1 or #2 smoke
spot on the Bacharach scale.
For additional burner component information, see
Burner Assembly Exploded View page.
It is recom-
mended that the oil burner be serviced yearly or as
needed. Contact your local service center.
Hotsy 800 OIL FIRED OPERATOR’S 8.921-206.0 - B