22 of 37
Indesit
Company
Service Manual UK
English
POWER MODULE Parameters
DEFROST HEATING ELEMENTS
FREEZER FAN OPERATION
Defrost Heating Elements -
The parameters utilised to start the
defrost cycle are as follows:
•
Compressor ON time since the last defrost cycle.
8 hours,
but the start time will reduce dependant on door
opening times.
•
The appliance is plugged in and switched on.
•
Total time since the last defrost cycle.
50 hours,
but the start time will reduce dependant on door
opening times.
The parameters utilised to end the
defrost cycle are as follows:
•
Maximum time defrost heater is ON.
Approximately 20 minutes
Defrost end temperature (freezer defrost cut-out).
+7°C ± 3°C
Freezer Fan Operation
-
The freezer fan is managed by the
power module and is switched on/off
after a preset time interval that is
parameterised in the memory after a
compressor start/stop.
After the defrost cycle
the fan starts after a timed interval
following a compressor start, also this interval is
parameterised in the memory;
Compressor 7 minutes PLUS 3 minutes for the Fan
= 10 minutes