4.4.
Gas Leak Control
The gas leak tests of the heater are carried out from the factory before
shipment. Once the device has been installed, it must be checked again, including
the complete gas connection line.
Isıtıcı gaz hattı,
hatta gaz verildikten sonra kontrol
edilmelidir.
•
Make sure that the gas valve on the heater is closed.
• Spray the foam made with a mixture of detergent and water or apply it to the
joints with a brush and check the formation of the balloons. If the balloon is formed,
there is a leak and close the gas inlet.
• Re
-tighten the leak connection, open the gas and check for leaks again.
• Do not smoke during the test.
• Continue to check for leaks at other connections.