6.6 Connecting to Electrical Power
Warning
THIS APPLIANCE MUST BE EARTHED
To prevent possible severe electrical shock or extensive damage
to the unit, the appliance must be connected via the flexible supply
cord supplied with the appliance to an appropriate outlet socket
installed in accordance with local codes and regulations i.e.
AS/NZS 3000
It is recommended that these appliances are connected to a separate 240VAC 50HZ electrical
supply, protected by an appropriate 15 A circuit breaker and Residual Current Device.
Check the serial plate on the appliance for the electrical supply requirements.
The service of a licensed electrician may be required to ensure the installation is in accordance
with the local codes and regulations.
Warning
If the supply cord is damaged, it must be replaced by the
manufacturer, its service agent or similarly qualified persons in order
to avoid a hazard.
6.7 Commissioning
The GP27hx uses plate heat exchanger technology. The Glycol Pump MUST be connected
and operational for the unit to work properly. If it desired to have the unit at operating
temperature prior to connecting to a python then a temporary connection from the pump outlet
to the glycol return must be fitted.
Top up the tank with premixed 30% glycol / water solution.
Check solution with refractometer
Turn power on to the unit. Ensure liquid level does not drop below pump intake during initial
filling of python.
If bath temperature is above unit set point, refrigeration should operate.
Check all connections for leaks