18
H. Water Supply and Drain Connections
See Fig. 14, 15, or 16
CAUTION
1. Normal operating water temperature should be 45 F to +90 F (+7°C
to +32°C). Operation of the icemaker, for extended periods, outside of this
normal temperature range may affect icemaker performance.
2. To prevent damage to equipment, do not operate the icemaker when the
water supply is off, or if the pressure is below 10 PSIG. Do not run the
icemaker until the proper water pressure is reached.
• Water supply and drain connections must be installed in accordance with applicable
national, state, and local regulations.
• A plumbing permit and services of a licensed plumber may be required in some areas.
• External filters, strainers, or softeners may be required depending on water quality.
Contact your local Hoshizaki distributor for recommendations.
1. Icemaker
• Water supply inlet is 1/2" female pipe thread (FPT). A minimum of 1/2" OD copper tubing
is recommended for the water supply line.
• A water supply line shut-off valve and drain valve should be installed.
• Water supply pressure should be a minimum of 10 PSIG and a maximum of 113 PSIG. If
the pressure exceeds 113 PSIG, the use of a pressure reducing valve is required.
• Icemaker drain outlet is 3/4" FPT. A minimum of 3/4" OD hard pipe is recommended for
the icemaker drain line. The icemaker drain line must be run separately from the storage
bin drain line.
6. Stacking Remote Condenser Unit
1) Install the lower remote condenser unit as described earlier in this section.
2) Place the upper remote condenser unit on top of the lower. See Fig. 13.
3) Secure the upper remote condenser unit with the 4 screws provided.
4) Install refrigerant lines, and make electrical connections for each fan motor as
described earlier in this section.
Fig. 13
Upper Remote
Condenser Unit
Screws
Lower Remote
Condenser Unit