4. Line Set
• Precharged tubing kits, available as optional equipment from HOSHIZAKI AMERICA, are
recommended. Field fabricated line sets are allowed, see instructions below.
• The maximum line length for the standard refrigerant charge is 66 feet. Should an
installation require a longer line length, additional refrigerant must be added. Add .4 oz.
of R-404A for each foot over 66 feet to a maximum of 100 feet or contact HOSHIZAKI
Technical Support at 1-800-233-1940 for recommendations.
• The maximum vertical distance between the remote condenser unit and the icemaker is
33 feet above or 10 feet below the icemaker. These distances are measured fitting to
fitting.
CAUTION
Failure to install the equipment within these guidelines may adversely affect
performance, component life, and warranty coverage.
Fig. 10
Hexagon Bolt
with Split Lock
Washer and
Flat Washer
M8
Hexagon Nut
3. Setup
1) Secure the legs to the remote condenser unit with eight M8×16 mm hexagon bolts and
M8 nuts as shown in the illustration. See Fig. 10.
2) The legs have eight mounting holes. Secure the legs with eight bolts (not included).