n) Anti-Slush Control (S2 dip switch 6) [Program Ver. 3.1]
Do not adjust. This must be left in the factory default position or the unit will not operate
properly.
When activated (Ver. 2.0), the thermistor located on the suction line checks for a 50°F
(10°C) temperature as the evaporator cools. When 50°F (10°C) is reached, a 3.9 kΩ
signal causes the control board to de-energize the pump motor for 10 seconds and
energize it for 50 seconds repeatedly. When 34°F (1°C) is reached, a 5.9 kΩ signal
causes the control board to de-energize the pump motor for 10 seconds, energize it for
50 seconds, de-energize it again for 10 seconds, then energize it continuously.
S2 Dip Switch Setting
Anti-Slush Control
No. 6
OFF
Activated (Ver. 2.0)
ON
Deactivated
o) Anti-Slush Control (S2 dip switch 6) [Program Ver. 3.2]
Do not adjust. This must be left in the factory default position or the unit will not operate
properly.
When activated (Ver. 1.1), the thermistor located on the suction line checks for a 41°F
(5°C) temperature as the evaporator cools. When 41°F (5°C) is reached, a 4.8 kΩ signal
causes the control board to de-energize the pump motor for 10 seconds.
When activated (Ver. 2.0), the thermistor located on the suction line checks for a 50°F
(10°C) temperature as the evaporator cools. When 50°F (10°C) is reached, a 3.9 kΩ
signal causes the control board to de-energize the pump motor for 10 seconds and
energize it for 50 seconds repeatedly. When 34°F (1°C) is reached, a 5.9 kΩ signal
causes the control board to de-energize the pump motor for 10 seconds, energize it for
50 seconds, de-energize it again for 10 seconds, then energize it continuously.
S2 Dip Switch Setting
Anti-Slush Control
No. 6
OFF
Activated (Ver. 1.1)
ON
Activated (Ver. 2.0)
[d] CONTROL BOARD CHECK PROCEDURE
Before replacing a control board that does not show a visible defect and that you
suspect is bad, always conduct the following check procedure. This procedure will help
you verify your diagnosis.
1) Check the dip switch settings to assure that S1 dip switch 3, 4, 7, 8, 9, & 10 and S2
dip switch 1 through 6 are in the factory default position. S1 dip switch 1, 2, 5, & 6 are
cleaning adjustments and the settings are flexible.