28
Door Switch and Door Alarm (Do Not Adjust)
Service Menu
Min.
Max.
Unit
Factory Setting
Description
L0
0
5
---
2
Door switch function.
1=compressor and evaporator
fan motor de-energized
2=evaporator fan motor
de-energized
3-5=reserved
L1
0
1
---
0
Door switch operation.
0=normally open
1=normally closed
L2
-1
120
min.
10
Door alarm time delay.
-1=deactivated
L3
-1
120
min.
-1
Evaporator fan motor off time
when door is open.
-1=until door switch engaged
L4
0
1
---
0
Save door alarm.
0=no
1=yes
L10
0
999
min.
20
Energy saving activation.
After cabinet temperature
is reached and door switch
remains closed.
Serial Network (Do Not Adjust)
Service Menu Min.
Max.
Unit
Factory Setting
Description
LA
1
247
---
247
Address (not used)
Lb
0
3
---
2
Baud Rate (not used)
LP
0
2
---
2
Parity (not used)