27
Evaporator Fan Motor (Do Not Adjust)
Service Menu
Min.
Max.
Unit
Factory Setting
Description
F0
0
4
---
1
Fan operation with door closed.
Do not adjust.
0=off
1=on: see also F13, F14, and L10
2=parallel with compressor
3= dependent on F1
4=disabled when compressor is off,
dependent on F1 when
compressor is on.
F1
-99
99
°C/°F
30
Fan off temperature when F0 set to
3 or 4. Do not adjust.
F2
0
2
---
1
Fan operation during defrost:
Do not adjust.
0=disabled
1=enabled
2=dependent on F0
F3
0
15
2
Maximum fan off time when defrost
thermistor used.
F7
-99
99
°C/°F
0
Fan on temperature when defrost
thermistor used.
F8
0.1
15
°C/°F
4
F1 differential.
F9
0
240
sec.
0
Energy saving evaporator fan motor
delay after compressor shuts off.
F13
0
240
min.
5
Energy saving evaporator fan motor
off time.
F14
0
240
min.
1
Energy saving evaporator fan motor
on time.