20
CONTROLS AND ADJUSTMENTS
DEFROST
SELECTOR
STEPS TO CHANGE SETPOINT
1. To access the menu press the “Set” button until the value “0” is
displayed on the screen.
2. Release the “Set” button.
3. Press the “Up” button repeatedly until the value 22 is displayed
on the screen. This is the password.
4. Push the “Set” button once to access the menu.
5. When you access the menu the display shows the letters “PS”.
6. Press the “Up” button repeatedly until “St” appears in the display,
then press the “Set” button.
7. The display shows the value of the current setpoint.
8. Change the value of the Set Point using the “Up” or “Down”
button.
9. To save the new Set Point, press the “Set” button until the display
shows the current temperature.
NOTES:
- THE DEFAULT SET POINT IS 34°F.
- THE SET POINT RANGE IS FROM 28°F TO 40°F.
ALARM SAFETIES
Alarm signals are designed to protect the appliance and items inside. These
alarms give information or warnings in the event the appliance is operating
out of acceptable parameters. Should one of the alarms accur, follow the
instructions below to address the alarm. The alarm icon appears on the
display and the alarm code alternates with the cabinet temperature. For
high temperature, low temperature, and door alarms, the appliance beeps
in addition to displaying the alarm icon and alarm code.