20
3. ELECTRONIC CONTROLS
[a] SET POINT TEMPERATURE (compressor OFF
temperature)
Off-cycle defrost (RTC series): -2 to +12°C
Heater defrost (FTC series): -23 to -7°C
[b] CABINET TEMPERATURE DIFFERENTIAL
4 K (from “set point temp” to “set point temp + 4 K”)
The compressor stops when the cabinet temperature reaches down to the set point
temperature, and starts when the cabinet temperature rises to the set point tempe
4°C. Accordingly, the average cabinet temperature will be around the set point temperature
+ 2°C.
[c] DEFROST CYCLE
The unit automatically defrosts the evaporator 3 hours (RTC series) or 6 hours (FTC
series) after the refrigeration starts. The defrost indicator light on the operation panel
comes on when the defrost cycle starts.
[d] DEFROST TERMINATION TEMPERATURE
Off-cycle defrost (RTC series): +5°C
Heater defrost (FTC series):
+20°C
[e] TEMPERATURE DISPLAY
During a defrost cycle, the screen indicates “dF” (FTC series only).
Average Cabinet
Temperature
Set Point Temperature
Compressor
ON
OFF
Time
4K
Interior Thermistor Temperature
Содержание FTC-120MDA
Страница 6: ...3 2 DIMENSIONS SPECIFICATIONS a RTC 120MNA ...
Страница 7: ...4 b RTC 120MDA ...
Страница 8: ...5 c RTC 150MNA ...
Страница 9: ...6 d RTC 150MDA ...
Страница 10: ...7 e RTC 180MNA ...
Страница 11: ...8 f RTC 180MDA ...
Страница 12: ...9 g FTC 120MNA ...
Страница 13: ...10 h FTC 120MDA ...
Страница 14: ...11 i FTC 150MNA ...
Страница 15: ...12 j FTC 150MDA ...
Страница 16: ...13 k FTC 180MNA ...
Страница 17: ...14 l FTC 180MDA ...
Страница 18: ...15 II TECHNICAL INFORMATION 1 WIRING DIAGRAM a RTC SERIES ...
Страница 19: ...16 b FTC 120MNA FTC 120MDA FTC 150MNA ...
Страница 20: ...17 c FTC 150MDA FTC 180MNA FTC 180MDA ...