63
2. LOW ICE PRODUCTION
PROBLEM POSSIBLE
CAUSE
REMEDY
1. Gas leaks.
1. See 1 - [5] - a).
2. Refrigerant line
clogged.
2. Replace the clogged
component.
a) Refrigerant Line
3. Overcharged.
3. Recharge.
1. Dirty Air Filter or
Condenser.
1. Clean.
2. Ambient or condenser
water temperature
too warm.
2. Check for recommended
temperature.
3. Condenser water
pressure too low or
off.
3. Check and get recommended
pressure.
4. Fan rotating too slow.
4. See 3 - [1] - a).
b) High-side
Pressure Too
High
5. Water Regulating
Valve clogged.
5. Clean.
c) Expansion Valve
(not adjustable)
1. Low-side pressure
exceeding the limit.
1. Replace.
[1] Low ice
production.
d) Evaporator
1. Evaporator pipe
crushed.
1. Replace.
3. OTHERS
PROBLEM
POSSIBLE CAUSE
REMEDY
1. Bearing worn out.
1. Replace.
2. Fan blade deformed.
2. Replace fan blade.
a) Fan Motor
(Condenser Unit)
3. Fan blade does not
move freely.
3. Replace.
1. Bearings worn out, or
cylinder valve broken.
1. Replace.
b) Compressor
2. Mounting pad out of
position.
2. Reinstall.
c) Refrigerant Lines
1. Rub or touch lines or
other surfaces.
1. Replace.
d) Gear Motor (Ice
Making)
1. Bearing or Gear
wear/damage.
1. Replace.
1. Low-side pressure too
low.
1. See if Expansion Valve Bulb is
mounted properly, and
replace the valve if necessary.
e) Evaporator
2. Scale on inside wall of
Freezing Cylinder.
2. Remove Auger. Use a solution
of lime removing cleaner to
clean periodically. If water is
found to surpass the following
levels, install a conditioner.
Hardness 50 ppm
Silica 30 ppm
f) Heater
1. Broken.
1. Replace.
[1] Abnormal noise
g) CPR (Condenser
Unit)
1. Internal leaks.
1. Replace.
Содержание FM-300AFE-HC
Страница 7: ...3 2 DIMENSIONS CONNECTIONS a FM 481AGE HC FM 481AGE HCN ...
Страница 8: ...4 b FM 300AFE HC FM 300AFE HCN ...
Страница 9: ...5 3 SPECIFICATIONS a FM 481AGE HC ...
Страница 10: ...6 b FM 481AGE HCN ...
Страница 11: ...7 c FM 300AFE HC ...
Страница 12: ...8 d FM 300AFE HCN ...
Страница 14: ...10 Drier Ice Chute Pressure Switch ...
Страница 23: ...19 b FM 300AFE HC FM 300AFE HCN Pressure Switch Cut out 22 6 1 5 0 bar Cut in 15 7 1 5 bar ...
Страница 24: ...20 2 WIRING DIAGRAM a WIRING DIAGRAM FM 481AGE HC FM 481AGE HCN ...
Страница 25: ...21 FM 300AFE HC FM 300AFE HCN ...
Страница 26: ...22 b CONTROL BOX LAYOUT FM 481AGE HC FM 481AGE HCN ...
Страница 27: ...23 FM 300AFE HC FM 300AFE HCN ...
Страница 35: ...31 FM 300AFE HC FM 300AFE HCN ...
Страница 36: ...32 ...
Страница 37: ...33 c SEQUENCE FM 481AGE HC FM 481AGE HCN 1 Startup Water Supply ...
Страница 38: ...34 FM 481AGE HC FM 481AGE HCN 2 Startup After completion of water supply Gear Motor and Fan Motor start 5 min ...
Страница 39: ...35 FM 481AGE HC FM 481AGE HCN 3 Startup Ice production starts ...
Страница 40: ...36 FM 481AGE HC FM 481AGE HCN 4 Normal Operation Bin Control ...
Страница 41: ...37 FM 481AGE HC FM 481AGE HCN 5 Shutdown Compressor stops 5 min ...
Страница 42: ...38 FM 481AGE HC FM 481AGE HCN 6 Shutdown Drain ...
Страница 43: ...39 FM 300AFE HC FM 300AFE HCN 1 Startup Water Supply ...
Страница 44: ...40 FM 300AFE HC FM 300AFE HCN 2 Startup After completion of water supply Gear Motor and Fan Motor start 5 min ...
Страница 45: ...41 FM 300AFE HC FM 300AFE HCN 3 Startup Ice production starts ...
Страница 46: ...42 FM 300AFE HC FM 300AFE HCN 4 Normal Operation Bin Control ...
Страница 47: ...43 FM 300AFE HC FM 300AFE HCN 5 Shutdown Compressor stops 5 min ...
Страница 48: ...44 FM 300AFE HC FM 300AFE HCN 6 Shutdown Drain ...