63
1) Turn off the power supply, and remove the panels.
2) For F-2000MLF, close the Shut-off Valves to the Compressor Rack Assembly.
3) Recover the refrigerant and store it in an approved container, if required by an applicable
law.
4) Remove the Expansion Valve Bulb at the Evaporator outlet.
5) Remove the Expansion Valve Cover, and remove the Expansion Valve using brazing
equipment.
6) Braze the new Expansion Valve with nitrogen gas flowing at the pressure of 3 - 4 PSIG.
WARNING
Always protect the valve body by using a damp cloth to prevent the valve
from overheating. Do not braze with the valve body exceeding 250°F.
5. REMOVAL AND REPLACEMENT OF EXPANSION VALVE
IMPORTANT
Sometimes moisture in the refrigerant circuit exceeds the Drier capacity
and freezes up at the Expansion Valve. Always install a new Drier every
time the sealed refrigeration system is opened. Do not replace the Drier
until after all other repairs or replacements have been made.
7) Install the new Drier [except F-2000MLF].
8) Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.
9) Evacuate the system. Charge it with refrigerant [except F-2000MLF]. For the water-
cooled models, see the Nameplate for the required refrigerant charge and type. For the
remote air-cooled models, see the label on the Control Box.
10) Attach the Bulb to the suction line. Be sure to secure the Bulb using a band and
to insulate it.
11) Place the new set of Expansion Valve Covers in position.
12) For F-2000MLF, open the Shut-off Valves to the Compressor Rack Assembly.
Содержание F-2000MLF
Страница 14: ...14 2 CONDENSER UNIT URC 20F...
Страница 16: ...16 II GENERAL INFORMATION 1 CONSTRUCTION F 2000MLF C...
Страница 17: ...17 F 2000MRF3 C F 2000MRF C...
Страница 18: ...18 F 2000MWF C...
Страница 20: ...20 F 2000MWF F 2000MRF C...
Страница 21: ...21 F 2000MLF C...
Страница 22: ...22 III TECHNICAL INFORMATION 1 WATER CIRCUIT AND REFRIGERATION CIRCUIT F 2000MLF C...
Страница 23: ...23 F 2000MRF3 C...
Страница 24: ...24 F 2000MWF C...
Страница 25: ...25 2 WIRING DIAGRAMS F 2000MLF C...
Страница 26: ...26 F 2000MRF3 C...
Страница 27: ...27 F 2000MWF C...
Страница 28: ...28 F 2000MRF C...
Страница 30: ...30 b When Reservoir has been filled Gear Motor starts immediately...
Страница 31: ...31 c Compressor starts F 2000MLF C only two solenoid valves open about 60 sec after Gear Motor starts...
Страница 33: ...33 e Low Water Except Water cooled Model where Compressor will operate intermittently...
Страница 39: ...39...
Страница 69: ...69...