B. Defrost
There are 2 types of defrost: Off Cycle Defrost and Heated Defrost.
Manual Initiation (All Models):
Turn the TD all the way to the right. Wait 3 sec. then
back to original setting. Defrost initiated.
Automatic Initiation
: 8-hr. or 6hr. Defrost timer terminates.
Manual Termination:
Turn the TD all the way to the right. Wait 3 sec. then back to
original setting. Defrost terminated.
Automatic Termination
: Cabinet temperature above setpoint, or defrost thermistor
above termination temperature, or back defrost timer terminates.
1. Undercounter and Worktop Refrigerators
Off-cycle defrost between run cycles.
III. Controls and Adjustments
A. Temperature Settings
1. Temperature Reading
A thermometer with both °F and °C scales is mounted in the cabinet. See Fig. 1.
2. Cabinet Temperature
The appliance features a cabinet temperature control dial (TD). The warmest setting
is 1 and the coldest setting is 7. See the table for default cabinet temperature control
settings.
Model
Default Cabinet Temperature
Control Setting
Approximate Default Temperature
Undercounter
Worktop
Between 4 and 5
Refrigerator: 34°F (1°C)
Freezer: -5°F (-21°C)
Prep Table
6
34°F (1°C)
Fig. 1
Thermometer
Cabinet Temperature
Control Dial
Warmer
Colder