II. Sequence of Operation and Service Diagnosis
The steps in the sequence are as outlined below.
See the table for default cabinet temperature control settings.
Model
Default Cabinet Temperature
Control Setting
Approximate Default Temperature
Undercounter
Worktop
Between 4 and 5
Refrigerator: 34°F (1°C)
Freezer: -5°F (-21°C)
Prep Table
6
34°F (1°C)
A1. Thermostat Control Sequence of Operation Flow Chart
1. Undercounter and Work Top: Refrigerator
Refrigerator Sequence Flow Chart
1. Startup/Cool Down
2. Cool Down Achieved
CTh
closed
Comp
energized
ConFM
energized
EvapFM
energized
CTh
open
EvapFM
energized CRMR60 and CRMR72
Comp
de-energized
ConFM
de-energized
EvapFM
de-energized CRMR27 and CRMR48
CTh in control
CTh above setpoint
CTh cools to setpoint
CTh abo
ve
setpoint
Off cycle defrost
between run cycles.
Legend:
Comp
-compressor
ConFM
-condenser fan motor
CTh
-cabinet thermostat
EvapFM
-evaporator fan motor